Electrical burner connection
1. Check that the connections "L 1"
and "N" are made correctly at the
power supply of the control unit.
Control unit installation
instructions
Danger
Incorrect core terminations
can cause severe injuries
and damage to the equip-
ment.
Cores "L 1" and "N" must
never be interchanged.
L1: brown
N:
blue
PE: green/yellow
2. Route the burner cables on the
hinge side of the door downwards
behind the r.h. or l.h. cover.
3. Push burner plugs fA and lÖ onto
the MatriX burner.
!
4.
Please note
Never allow cables/leads to
come into contact with hot
components.
Secure the burner cables at the top
front panel and at the r.h. or l.h.
side of the cover using cable ties.
For this, use holes A in the panel
returns.
When using the stainless steel flue
gas header for two-boiler systems
(accessories):
Installation instructions, flue
gas header (accessories) for
two-boiler systems.
19