Lennox Signature Collection XP15 Installation Instructions Manual page 8

Signature collection xp15 units
Hide thumbs Also See for Signature Collection XP15:
Table of Contents

Advertisement

Table 2. Wire Run Length
Wire Run Length
AWG #
Insulation Type
less than 100' (30m)
18
color-coded, temperature
more than 100' (30m)
16
rating 35°C minimum
1. Install room thermostat
(ordered separately)
on an
inside wall approximately in the center of the area and
5 feet (1.5 m) from the floor. Do not install on an outside
wall or where sunlight, drafts or vibrations affect it.
2. Install low voltage wiring from outdoor to indoor unit
and from thermostat
to indoor unit as illustrated in
figure 14.
3. Install line voltage power supply to unit from a properly
sized disconnect switch as illustrated in figure 15.
4. Ground unit from ground lug as illustrated in figure 15
to unit disconnect switch, or to an earth ground.
LI
_._
z_
RTI$
AMBIENT
SENSOR
@
R721
DEFROST
COIL
SENSOR
S4HIGH
PRESSURE
SWITCH
$87
LOW
PRESSURE
SWITCH
©
LI
REVERSING
VALVE
©
LZ_
OMPRESSOR
CONTACTOR
54O
AI32
BI
HRI
A
w
AI32
A
EQUIPMENT
GROUND
COMPRESSOR
CONTACTOR
BLACK
TBI
(W5_
(W8
"-(v _
G
©
@
CB31MV
CBX32MV
A2 SIGNATURE
81M2B
TWISTEO
PAIR
I
A
NOTE
FOR
USE
WITH
COPPER
CONDUCTORS
ONLY.
REFER
TO
UNIT
RATING
PLATE
FOR
MINIMUM
CIRCUIT
AMPACITY
AND
MAXIMUM
OVER
CURRENT
PROTECTION
SIZE
A
REFER
TO
COMPRESSOR
N UNIT
FOR
ACTUAL
TERMINAL
mRmANGEMENT.
Z_
WARNING
ELECTRIC
SHOCK
HAZARD,CAN
CAUSE
INJURY
OR
DEATH.UNIT
MUST
BE
GROUNDED
IN
ACCOROANCE
WITH
NATIONAL
AND
LOCAL
CODES.
A
RTI4
SENSOR,
OUTDOOR
TEMP
(OPTIONAL)
LINE
VOLTAGE
FIELD
INSTALLED
CLASS
II
VOLTAGE
FIELD
INSTALLED
Figure
14. Typical
Low-Voltage
Field Wiring
GROUND
208-230/60/1
L1
L2
K1-1 COMPRESSOR
CONTACTOR
GROUNDLUG
CONTROLBOX
_'-
CONTACTOR
DEFROST
CONTROL
BOARD
(DCB)
-''_/
L_)NNN TOoXR t LYs'<
oTE_
OPERATION
"__
_[3_/
_
CAPACITOR
WARNING! - ELECTRIC SHOCK HAZARD. Can cause INJURY or DEATH. Unit must be grounded in accordance with national and local codes.
NOTE - For use with copper conductors only. Refer to unit rating plate for minimum circuit ampacity and maximum over-current protection size.
Figure 15. Typical High-Voltage Field Wiring
(Unit Panel)
505328M
04/08
Page 8