Lennox Signature Collection XP15 Installation Instructions Manual page 25

Signature collection xp15 units
Hide thumbs Also See for Signature Collection XP15:
Table of Contents

Advertisement

Table 16. DCB Diagnostic LEDs
DS2
DS1
Condition
Possible Cause(s)
Solution
Green
Red
1 Check control transformer power (24V).
No power (24V) to DCB terminals R and
2 If power is available to DCB and LED(s) do not light,
OFF
OFF
Power problem
C or DCB failure.
replace DCB.
SIMULTANEOUS
Unit operating
normally or in standby
None required.
SLOW FLASH
Normal operation
mode.
ALTERNATING
Initial power up, safety trip, end of room
None required (Jumper TEST pins to override)
SLOW FLASH
5-minute anti-short cycle delay
thermostat demand.
SIMULTANEOUS
Sensor
being detected
open or shorted
or out of temperature
range. DCB will revert to
FAST FLASH
Ambient sensor problem
time/temperaturedefrost
operation. (System will still heat or cool).
ALTERNATING
Sensor being detected open or shorted or out of temperature range. DCB will not perform demand
FAST FLASH
Coil sensor problem
or time/temperature
defrost operation. (System will still heat or cool).
ON
Indicates that DCB has internal component failure. Cycle 24 volt power to DCB. If code does not
ON
DCB failure
clear, replace DCB.
FAULT and LOCKOUT CODES
(Each fault adds 1 strike to that code's counter; 5 strikes per code = LOCKOUT)
1 Remove any blockages or restrictions from coils
SLOW
OFF
FLASH
Low pressure fault
OFF
ON
Low pressure lockout
SLOW
FLASH
OFF
High pressure fault
ON
OFF
High pressure lockout
1 Restricted air flow over indoor or out-
door coil.
2 Improper refrigerant charge in sys-
tem.
3 Improper metering device installed or
incorrect operation of metering de-
vice.
4 Incorrect or improper sensor location
or connection to system.
2
3
4
and/or fans. Check indoor and outdoor fan motor for
proper current draws.
Check system charge using approach and
subcooling temperatures.
Check system operating pressures and compare to
unit charging charts.
Make sure all pressure switches and sensors have
secure connections to system to prevent refrigerant
leaks or errors in pressure and temperature
measurements.
SLOW
Discharge
line
temperature
FLASH
ON
fault
FAST
FLASH
ON
FAST
OFF
FLASH
FAST
FLASH
OFF
Discharge line temperature
Lockout
Discharge sensor fault
Discharge sensorlockout
This code detects shorted sensor or high discharge temperatures. If the discharge line temperature
exceeds a temperature of 300°F (148°C) during compressor operation, the board will de-energize
the compressor contactor output (and the defrost output if active). The compressor will remain off
until the discharge temperature has dropped below 225°F (107°C).
The board detects open sensor or out of temperature sensor range. This fault is detected by allow-
ing the unit to run for 90 seconds before checking sensor resistance. If the sensor resistance is not
within range after 90 seconds, the board will count one fault. After five faults, the board will lockout.
SLOW
Discharge
line
temperature
FLASH
ON
fault
FAST
Discharge line temperature
FLASH
ON
lockout
FAST
FLASH
OFF
Some heat pump units do not use a defrost line sensor. Therefore this code is not applicable.
Some heat pump units do not use a defrost line sensor. However, on these units a resistor is
OFF
Discharge sensor fault
installed across pins P4-1 and P4-2. If the resistor is missing or damaged then this fault code will
be displayed.
FAST
Discharge sensor lockout
FLASH
Some heat pump units do not use a defrost line sensor. Therefore this code is not applicable.