Operating Instructions

5.1 Connection Scheme

SBR-FX/RMD includes a CAN segment which
can be connected by a plug of type D-Sub9.
Pin
Name
1
2
CAN_L
3
GND
4
5
SHLD
6
7
CAN_H
8
VCC
9
The device is supplied via a terminal block.
Pin 1
VCC
Pin 2
VCC
Pin 3
GND
Pin 4
GND
EMS Dr. Thomas Wünsche
User Manual
Function
Reserved
CAN_L signal line
(dominant low)
Ground
Reserved
Shield
Reserved
CAN_H signal line
(dominant high)
Output 5V (max. 150mA)
Reserved
Supply 24V
Supply 24V
Ground
Ground
13
User Manual
A serial connector of the type D-Sub9 allows
the configuration of SBR-FX/RMD.
Pin
Name
Function
2
RXD
Receiving data line
3
TXD
Sending data line
4
DTR
(Currently not supported)
5
GND
Ground
6
DSR
(Currently not supported)
The optical connection is realized by a pair of
single mode fibers (9/125µm diameter) con-
nected via LC terminals.

5.2 Router Correction Time and Cascading

The values listed below are typical values and
should fit most system configurations. The va-
lues to be used in a specific system may vary
based on parameters like busload and num-
bers of nodes. The use of a router may require
higher values for the Event Timeout settings.
If cascading is used, the Correction Time will
increase by the values of the following table
for each additional segment.
Baudrate
20 kb/s
50 kb/s
125 kb/s
250 kb/s
500 kb/s
14
EMS Dr. Thomas Wünsche
SBR-FX/RMD
Correction Time
25 ms
11 ms
5 ms
5 ms
5 ms