Flagro FLE-150 Operating Instructions Manual

Flagro FLE-150 Operating Instructions Manual

Industrial / commercial electric heater

Advertisement

OPERATING INSTRUCTIONS MANUAL
FLE-150
INDUSTRIAL / COMMERCIAL ELECTRIC HEATER
(OPERATOR MUST RETAIN FOR FUTURE REFERENCE)
Suitable for indoor or outdoor installation / Unvented / Unattended Type
26 Benfield Drive, St.Catharines, Ontario Canada L2S 3V5
(P) 905-685-4243 - (F) 905-685-0113

Advertisement

Table of Contents
loading

Summary of Contents for Flagro FLE-150

  • Page 1 OPERATING INSTRUCTIONS MANUAL FLE-150 INDUSTRIAL / COMMERCIAL ELECTRIC HEATER (OPERATOR MUST RETAIN FOR FUTURE REFERENCE) Suitable for indoor or outdoor installation / Unvented / Unattended Type 26 Benfield Drive, St.Catharines, Ontario Canada L2S 3V5 (P) 905-685-4243 - (F) 905-685-0113...
  • Page 2 FLE-150 OPERATING INSTRUCTIONS MANUAL GENERAL HAZARD WARNING: FAILURE TO COMPLY WITH THE PRECAUTIONS AND INSTRUCTIONS PROVIDED WITH THIS HEATER, CAN RESULT IN DEATH, SERIOUS BODILY INJURY AND PROPERTY LOSS OR DAMAGE FROM HAZARDS OF FIRE, EXPLOSION BURN ASPHYXIATION, OR ELECTRICAL SHOCK...
  • Page 3 Introduction You have just received an FLE-150 150kW Electric Construction Heater manufactured by Flagro Industries. Use: The FLE-150 Electric Construction Heater is designed for temporary heat only. The heater may be installed indoors or out and used to bring 100% outdoor air, or heat and re-circulate building air.
  • Page 4: Maintenance

    MAINTENANCE Every heater should be inspected before each use, and at least annually by a qualified service person The appliance must be kept clear and free from combustible materials, gasoline and other flammable vapors and/or liquids The flow of ventilation air must not be obstructed. Be sure to check the fan assembly and ensure the motor and blade are operating properly.
  • Page 5: Start-Up Instructions

    START UP INSTRUCTIONS Determine power source - 480V (confirm power source is correct) Remove top cover and inspect all wiring (once complete, secure top cover to heater using the same hardware) Connect Flanged Camlocks to female camlocks ( colour coded) Connect camlocks as follows: Black Blue...
  • Page 6 Notes: Speed inverter is pre-set for optimum air flow/temperature rise. Based on kW selection, blower will adjust speed. See Chart below HEAT SETTING BTUH TEMP. RISE NOISE RATING 150 kW 512,000 5300 138F 79 DB 90 kW 307,000 4650 101F 76 DB 60kW 205,000...
  • Page 7: Heater Specifications

    26 Benfield Dr. St.Catharines, Ontario Canada L2S 3V5 (O) 905-685-4243 (F) 905-685-0113 HEATER SPECIFICATIONS MODEL FLE150 Power Requirements 480V MAXIMUM INPUT (KW) 512,000 btu BLOWER 7 1/2 H.P. TEMPERATURE RISE 60KW 67 F (above ambient) 90KW 101 F 150 KW 138 F AMP DRAW MOTOR...
  • Page 8 FLE-150– PARTS LIST 150KW RESISTOR ELEMENT FAN BLADE ASSEMBLY 7.5 HP MOTOR FLE- 1503 (480 VOLT) FLE-1501 (480 VOLT) FLE- 1503A (575VOLT) FLE-1501A FLE-1502 (575 VOLT) VARIALBLE SPEED DRIVE FUSES TRANSFORMER FLE-1509 - 125 Amp Class T FLE-1510 - 90 Amp Class T...
  • Page 9: High Limit

    FLE-150 PARTS LIST AIR PROVING SWITCH HIGH LIMIT 2 POSITION SWITCH (250-F) FLE-633 60KW 90KW FLE-1512 FLE-1513 THERMOSTAT/MANUAL BLOWER ON/OFF EMERGENCY STOP BUTTON GREEN AIR PROVEN LIGHT HIGH LIMIT/AIR PROVEN LIGHT FLE-634 FLE-636 FLE-635 THERMOSTAT N/C CONTACT BLOCK N/O CONTACT BLOCK...
  • Page 10 FLE-150 PARTS LIST WHEELS CAM-LOCK DETACHABLE INLET GUARD FLE-615 – BLUE FLE-609 – 6” LOCKABLE FLE-616 – BLACK FLE-1514 FLE-610 – 6” RIGID FLE-617 – GREEN FLE-618 - RED CAM-LOCK - PANEL SNAP COVERS - PANEL FLE-611 – BLUE FLE-611A – BLUE FLE-612 –...
  • Page 11: Body Panels

    BODY PANELS DESCRIPTION FLE-150FR OUTER FRAME FLE-157 RIGHT SIDE PANEL FLE-158 LEFT SIDE PANEL FLE-159 REAR PANEL FLE-160 FRONT PANEL FLE-162 TOP PANEL FLE-162B TOP PANEL ACCESS DOOR FLE-170 CONTROL PANEL RAIN GUARD...
  • Page 12: Fan Blade Assembly

    PARTS LIST FOR FLE-150 Part Number Part Description FLE-1501 150KW RESISTOR ELEMENT (480 VOLT) FLE-1502 FAN BLADE ASSEMBLY FLE-1503 7.5 HP MOTOR (480 VOLT) FLE-1504 VARIABLE SPEED DRIVE (480 VOLT) FLE-1505 WIRED CONTROL/OPERATOR PANELS (480 VOLT) FLE-1507 90 AMP 3P CONTACTOR (TWO PER HEATER)
  • Page 13 FLE-631 1/2 AMP CLASS CC TIME DELAY (TWO REQUIRED) FLE-632 5 AMP AGC GLASS FUSE FLE-633 TWO POSITION SWITCH FLE-634 EMERGENCY STOP BUTTON FLE-635 RED HIGH LIMIT/NON PROVEN AIR LIGHT (TWO PER HEATER) FLE-636 GREEN AIR PROVEN LIGHT FLE-637 BULBS FOR FLE-635/FLE-636 FLE-638 OPERATOR BLOCK FOR FLE-635/FLE-636 FLE-639...
  • Page 14: Troubleshooting

    TROUBLE SHOOTING PROBLEM PROBABLE CAUSE REMEDY PARTS Heater will not start No power to unit Make sure Master pull button is in the out Controller display does not position. illuminate Check voltage at main power supply and circuit breaker. Blown fuse(s) Check control panel fuses, replace if necessary.