Test Run - Fujitsu Ceiling Type Installation Manual

Indoor unit floor/ceiling type air conditioner
Table of Contents

Advertisement

(2)
Set the R.C. address (DIP switch setting)
Set the R.C. address of each indoor unit using the DIP switches on the indoor unit
circuit board. (See the following table and fi gure.)
The DIP switches are normally set to make the R.C. address 00.
Indoor unit
R.C. address
1
00
OFF
01
ON
02
OFF
03
ON
04
OFF
05
ON
06
OFF
07
ON
08
OFF
09
ON
10
OFF
11
ON
12
OFF
13
ON
14
OFF
15
ON
NOTE
Be sure to set the R.C. address sequentially.
Outdoor
unit 1
Remote
Indoor
unit 1
controller
R.C. address
00
(DIP switch setting)
: Transmission cable, Power supply cable
: Remote controller cable
Settings when simultaneous Multi is included
(3)
Set the refrigerant circuit address (Remote controller setting)
1.
Turn on all of the indoor units.
* Turn on the indoor unit with the R.C. address 00 last.
(Within 1 minute)
2.
Set the refrigerant circuit address.
Assign the same number to all of the indoor units connected to an outdoor unit.
(The unit is factory-set to "00")
Refrigerant circuit address
00
01
14
15
(4)
Set the "primary" and "secondary" settings. (Remote controller setting)
(Set the indoor unit that is connected to the outdoor unit using a transmission cable as the
"primary".)
Function Number
Primary
Secondary
After completing the function settings, turn off all of the indoor units,
and then turn them back on.
* If error code 21, 22, 24, or 27 is displayed, there may be an incorrect
setting. Perform the remote controller setting again.
NOTE
When different indoor unit models are connected using the group control system, some
functions may no longer be available.
If the group control system contains multiple units that are operated simultaneously, con-
nect and set the units as shown below.
Auto-changeover operates under the same mode with model R.C. address 00.
It should not be connected to any other Gr that is not of the same series (A**G only).
DIP SWITCH No.
2
3
4
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
Outdoor
Outdoor
Outdoor
unit 2
unit 3
unit 4
Indoor
Indoor
Indoor
unit 2
unit 3
unit 4
01
02
03
: Power supply cable
: Bus wire
Function Number
Setting Value
02
00
15
Setting Value
00
51
01
Standard
Standard
pair
pair
Outdoor
Outdoor
unit 1
unit 2
Remote
Indoor
Indoor
controller
unit 1
unit 2
R.C. address
(DIP switch setting)
Refrigerant circuit
address setting
(Function number 02)
Primary/Secondary setting
(Function number 51)
: Transmission cable, Power supply cable
: Remote controller cable
9.4.3. Dual remote controllers
2 separate remote controllers can be used to operate the indoor units.
The timer and self-diagnosis functions cannot be used on the secondary unit of remote
controller.
(1)
Wiring method (indoor unit to remote controller)
Indoor unit
When ground wire
is necessary
Primary unit
Remote
controller
(2)
Remote controller DIP switch 1 setting
Set the remote controller DIP switch 1-No. 2 according to the following table.
Primary unit
Secondary unit

10. TEST RUN

CHECK ITEMS
(1)
Is operation of each button on the remote controller normal?
(2)
Does each lamp light normally?
(3)
Do not air fl ow direction louvers operate normally?
(4)
Is the drain normal?
(5)
Is there any error noise and vibration during operation?
Do not operate the air conditioner in the running state for a long time.
Test running
When the air conditioner is run by pressing the remote controller test run button, the
OPERATION and TIMER Lamps fl ash slowly at the same time.
[Operation method]
For the operation method, refer to the operating
manual.
The outdoor unit may not operate depending on the
room temperature. In this case, press the TEST RUN
button on the remote controller while the air condi-
tioner is running. (Point the transmitter section of
the remote controller toward the air conditioner and
press the TEST RUN button with the tip of a ballpoint
pen, etc.)
To end test operation, press the remote controller
START/STOP button. (When the air conditioner
is running by pressing the TEST RUN button, the
OPERATION Lamp and TIMER Lamp will simultane-
ously fl ash slowly.)
Simultaneous
Simultaneous
twin
triple
Outdoor
Outdoor
unit 3
unit 4
Indoor
Indoor
Indoor
Indoor
unit 3
unit 4
unit 5
unit 6
: Power supply cable
: Bus wire
Remote controller cable
1 2 3
1 2 3
1 2 3
Secondary
unit
Remote
controller
DIP SW 1-No. 2
OFF
ON
Transmitter section
TEST RUN button
Indoor
unit 7
En-12