Field
Inverter Stacking
Stack Mode
Mode = Master:
Power Save
Mode = Slave:
Ranking
Mode = B Phase Master
Mode = C Phase Master: Master Power Save Level
Grid-Tie Enable
Grid-Tie Sell
Sell Voltage
Module Control
Module Control
Grid AC Input Voltage
Gen AC Input Voltage
Calibrate
Output Voltage
Battery Voltage
Grid Interface Protection Menu
Operating Frequency
Operating Frequency
Stage 1 Voltage Trip
Over Voltage Clearance Time
Over Voltage Trip
Under Voltage Clearance Time
Under Voltage Trip
Stage 2 Voltage Trip
Over Voltage Clearance Time
Over Voltage Trip
Under Voltage Clearance Time
Under Voltage Trip
Frequency Trip
Over Frequency
Clearance Time
Over
Frequency
Trip
Under Frequency
Clearance Time
Under
Frequency
Trip
Clearance Time
Mains Loss
Reconnect Delay
Maximum
Sell Current Limit
Sell Current
900-0145-01-01 Rev A
Table 16
Radian Inverter Settings
Item
Master Power Save Level
Slave Power Save Level
Master Power Save Level
GS7048E
GS3548E
X
X
X
X
X
X
X
X
X
X
X
X
X
X
50-Hz system
X
60-Hz system
X
50-Hz system
X
60-Hz system
X
X
GS7048E
X
GS3548E
Default
Minimum
Master
Master, Slave, B Phase Master, C Phase Master
0
0
1
1
0
0
0
0
Y
52.0 Vdc
44.0 Vdc
Auto
Left
0 Vac
–7 Vac
0 Vac
–7 Vac
0 Vac
–7 Vac
0.0 Vdc
–0.8 Vdc
50 Hz
1.5 seconds
0.12 seconds
252 Vac
240 Vac
1.5 seconds
0.12 seconds
208 Vac
160 Vac
0.2 seconds
0.12 seconds
264 Vac
240 Vac
0.2 seconds
0.12 seconds
196 Vac
160 Vac
0.2 seconds
0.12 seconds
51.0 Hz
50.1 Hz
61.0 Hz
60.1 Hz
0.2 seconds
0.12 seconds
47.0 Hz
45.0 Hz
57.0 Hz
55.0 Hz
2.0 seconds
1.0 seconds
300 seconds
2 seconds
30 Aac
5 Aac
15 Aac
5 Aac
Specifications
Maximum
31
31
31
31
Y or N
64.0 Vdc
Auto, Left, Right, Both
Auto, Left, Right, Both
7 Vac
7 Vac
7 Vac
0.8 Vdc
50 Hz, 60 Hz
4.0 seconds
300 Vac
4.0 seconds
240 Vac
4.0 seconds
300 Vac
4.0 seconds
240 Vac
5.0 seconds
55.0 Hz
65.0 Hz
5.0 seconds
49.9 Hz
59.9 Hz
5.0 seconds
302 seconds
30 Aac
15 Aac
69