SECTION 10: WIRING
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Heater must be properly grounded.
Failure to follow these instructions can result
in death or electrical shock.
FIGURE 19: Line Voltage Power Wiring
120 V-60 Hz
Supply Circuit
L1
L2
Gnd.
Burner 1
Gnd.
H
N
NOTE: The burners must have an uninterrupted 120 V, 60 Hz, 1 Ø power supply.
All burners are powered by a circuit(s) seperate from the brooder controller outputs.
Heater must be grounded in accordance with
applicable codes: United States: refer to National
Electrical Code
NFPA 70 - latest revision
®
Canada: refer to Canadian Electrical Code, CSA
C22.1 Part I - latest revision.
If any of the original internal wiring must be replaced,
it must be replaced with wiring materials having a
temperature rating of at least 105°C and 600 Volts.
10.1 Heater Wiring for use with Brooder Contoller
The heater will automatically modulate when
connected to an output relay on a brooder controller.
10.1.1 Line Voltage Power Wiring
All burners are powered by a circuit(s) separate from
the brooder controller outputs. The burners must
have an uninterrupted 120 V, 60 Hz, 1 Ø power
supply.
Burner 2
Gnd.
H
N