Horizontal Venting; Vertical Venting; Unvented Operation Tube Termination; Length Requirements - HeatRite VM-80 Installation, Operation & Service Manual

Gas-fired, low intensity unitary heater
Table of Contents

Advertisement

VM-S
I
, O
ERIES
NSTALLATION
PERATION AND

8.3 Horizontal Venting

In noncombustible walls only, vent terminal
(P/N 02537801-1P) may be used.
For 4" (10 cm) vents in either combustible or
noncombustible walls, use Tjernlund VH1-4 (P/N
90502100) or equivalent, insulated vent terminal.
Follow the manufacturer's instructions for proper
installation.
For 6" (15 cm) common vents in either combustible
or noncombustible walls, use Tjernlund VH1-6 (P/N
90502101) or equivalent, insulated vent terminal.
Follow the manufacturer's instructions for proper
installation.

8.4 Vertical Venting

For 4" (10 cm), an approved vent cap
(P/N 90502300) must be used.
For 6" (15 cm) common vent, an approved vent cap
(P/N 90502302) must be used.
For common vertical venting of more than two
heaters, See Page 34, Section 8.10.
A vent shall not extend less than 2' (.6m) above the
highest point where it passes through a flat roof of a
building.

8.5 Unvented Operation Tube Termination

Turndown type vent terminal with a screen must be
installed at the exhaust end of the tube. Vent terminal
design shall not incorporate backdraft flap.

8.7 Horizontal Ventilation 4" (10 cm) Pipe

Vent Adapter
4" (10 cm)
Single Wall Pipe
Description
Vent Terminal (Comb. Wall)
Vent Terminal
32 of 71
S
M
ERVICE
ANUAL
Combustible or
Non-Combustible Wall
4" (10 cm) Single Wall Pipe
Vent Terminal
Part Number
90502100
02537801-XX

FIGURE 17: Tube Termination

8.6 Length Requirements

The maximum vent length allowed is 45' (13.7 m).
The maximum outside air supply duct length allowed
is 45' (13.7 m).
The total vent length, plus outside air duct length and
any extensions to minimum heat exchanger lengths,
cannot exceed 65' (19.8 m).
Vent length should be limited to less than 20' (6 m).
If using extended heater lengths or vent lengths
greater than 20' (6 m), condensation will form in the
vent pipe. Insulation and additional sealing measures
(high temperature silicone at all seams) are required.
Optional heat exchanger beyond minimum lengths
are considered as vent length for length
determination.
Subtract 15' (4.6 m) of maximum allowed vent or duct
length per vent elbow if more than two are used.
SIDE VIEW
Non-Combustible Wall Only
Vent Adapter
18" (46 cm)
Min.
Vent Terminal