Turbulator Installation - HeatRite VM-80 Installation, Operation & Service Manual

Gas-fired, low intensity unitary heater
Table of Contents

Advertisement

VM-S
I
, O
ERIES
NSTALLATION
PERATION AND
Step 6.3.2 Coupling and Tube Assembly (Continued)
7' 6" ± 1'
(229 cm ± 25 cm)
Step 6.4 Turbulator Installation
Turbulator
Section
Turbulator
Adapter
Description
Turbulator Adapter
Turbulator Section
Tube
18 of 71
S
M
ERVICE
ANUAL
10' ± 1'
(305 cm ± 25 cm)
Tab
Part Number
03051503
03051504
91409XXX
Total Overall
Tube Length
Turbulator must be installed in
the last standard section of
tube. Turbulator is not required
on the VM-200.
Fold tab around outside
of tube nearest to the vent to
hold turbulator in place.
Tube Length
Model
Minimum
VM-80
20' (6 m)
VM-115
30' (9 m)
VM-150
40' (12 m)
VM-200
50' (15 m)

Turbulator Installation

VM-80
2nd 10' Section
VM-115
3rd 10' Section
VM-150
4th 10' Section
VM-200
N/A
Pull String

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vm-150Vm-115Vm-200