how do i reset after i change oil
1 comments:
Mr. Anderson
May 14, 2025
To reset a Generac 45kW generator after changing the oil, follow these steps:
1. Install the oil dipstick, check oil level, and ensure it's between the ADD and FULL marks. 2. Start the engine and check for oil leaks. 3. Shut off the engine and wait 10 minutes for the oil to settle. 4. Recheck the oil level and ensure it is not above the FULL mark. 5. Dispose of used oil properly. 6. Pull up the rubber flap and install the 7.5 amp fuse in the fuse holder. 7. Install the T1 fuse in the transfer switch. 8. Press AUTO on the control panel; the green LED should turn on. 9. Move the Main Circuit Breaker switch to the ON (Closed) position. 10. Close the viewing window. 11. Remove any DO NOT OPERATE tags or placards. 12. Reset the time and date on the control panel.
Need help?
Do you have a question about the 45kW and is the answer not in the manual?
Questions and answers
how do i reset after i change oil
To reset a Generac 45kW generator after changing the oil, follow these steps:
1. Install the oil dipstick, check oil level, and ensure it's between the ADD and FULL marks.
2. Start the engine and check for oil leaks.
3. Shut off the engine and wait 10 minutes for the oil to settle.
4. Recheck the oil level and ensure it is not above the FULL mark.
5. Dispose of used oil properly.
6. Pull up the rubber flap and install the 7.5 amp fuse in the fuse holder.
7. Install the T1 fuse in the transfer switch.
8. Press AUTO on the control panel; the green LED should turn on.
9. Move the Main Circuit Breaker switch to the ON (Closed) position.
10. Close the viewing window.
11. Remove any DO NOT OPERATE tags or placards.
12. Reset the time and date on the control panel.