Gas Manifold Pressurem; Easurement And Djustment; A Djustment - Amana GDH8 Installation Instructions Manual

Gas furnace
Hide thumbs Also See for GDH8:
Table of Contents

Advertisement

1. Turn OFF gas to furnace at the manual gas shutoff valve
external to the furnace.
2. Connect a calibrated water manometer (or appropriate
gas pressure gauge) at either the gas valve inlet pressure
Tap or the gas piping drip leg. See Honeywell gas valve
figure or White-Rodgers gas valve figure for location of
inlet pressure Tap.
NOTE: If measuring gas pressure at the drip leg or Honeywell
gas valve, a field-supplied hose barb fitting must be installed
prior to making the hose connection. If using the inlet pressure
Tap on the White-Rodgers gas valve, then use the 36G Valve
Pressure Check Kit, Goodman Part No. 0151K00000S.
3. Turn ON the gas supply and operate the furnace and all
other gas consuming appliances on the same gas supply
line.
4. Measure furnace gas supply pressure with burners firing.
Supply pressure must be within the range specified in
the Inlet Gas Supply Pressure table.
INLET GAS SUPPLY PRESSURE
Natural Gas
Minimum: 4.5" w.c.
Propane Gas
Minimum: 11.0" w.c.
If supply pressure differs from table, make the necessary ad-
justments to pressure regulator, gas piping size, etc., and/or
consult with local gas utility.
5. Turn OFF gas to furnace at the manual shutoff valve and
disconnect manometer. Reinstall plug before turning on
gas to furnace.
6. Turn OFF any unnecessary gas appliances stated in
step 3.
Gas Line
Gas
Shutoff
Valve
Drip Leg Cap
With Fitting
Measuring Inlet Gas Pressure (Alt. Method)
Maximum: 10.0" w.c.
Maximum: 13.0" w.c.
Gas Line
To Furnace
Manometer Hose
G
M
P
AS
ANIFOLD
RESSURE
T
O PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE
GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING
. O
PLATE
NLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING
THE GAS VALVE PRESSURE REGULATOR
HIGH VOLTAGE !
D
ISCONNECT ALL POWER BEFORE SERVICING OR
. M
INSTALLING THIS UNIT
ULTIPLE POWER SOURCES MAY
. F
BE PRESENT
AILURE TO DO SO MAY CAUSE PROPERTY
,
DAMAGE
PERSONAL INJURY OR DEATH
M
S
ODELS USING
INGLE
This valve is shipped from the factory with the regulator preset
(see control label).
Consult the appliance rating plate to ensure burner manifold
pressure is as specified. If another outlet pressure is required,
follow these steps.
1. Turn OFF gas to furnace at the manual gas shutoff valve
external to the furnace.
2. Turn OFF all electrical power to the system.
3. Outlet pressure tap connections:
a. Honeywell valve:
Remove the outlet pressure Tap plug. Install an 1/8"
NPT hose barb fitting into the outlet pressure tap.
b. White-Rodgers valve:
Back outlet pressure test screw (outlet pressure Tap)
out one turn (counterclockwise, not more than one
turn).
4. Attach a hose and manometer to the outlet pressure
barb fitting (Honeywell valve) or outlet pressure Tap (White-
Rodgers valve).
5. Turn ON the gas supply.
6. Turn ON power and close thermostat "R" and "W"
contacts to provide a call for heat.
7. Using a leak detection solution or soap suds, check for
leaks at outlet pressure Tap plug (Honeywell valve) or
screw (White-Rodgers valve). Bubbles forming indicate
a leak. SHUT OFF GAS AND REPAIR ALL LEAKS
IMMEDIATELY!
8. Measure the gas manifold pressure with burners firing.
Adjust manifold pressure using the Manifold Gas
Pressure table shown below.
Manifold Gas Pressure
Natural Gas
Propane Gas
28
M
A
EASUREMENT AND
CAUTION
.
WARNING
.
S
G
V
TAGE
AS
ALVES
3.5" w.c.
10.0" w.c.
DJUSTMENT
,
THE