Fireplace Vent Connection - Napoleon BGD40-P Installation And Operation Instruction Manual

Natural and propane gas
Table of Contents

Advertisement

6. Aligning the seams of the
terminal and air terminal connector,
place the terminal over the air
terminal connector making sure
the liner goes into the hole in the
terminal. Secure with the three
screws provided.
7. Apply a heavy bead of
weatherproof caulking 2"
above the fl ashing. NOTE:
Maintain a minimum 2" space
between the air inlet base
and the storm collar. Install
the storm collar around the
air terminal and slide down
to the caulking. Tighten to
ensure that a weather-tight seal between the air terminal
and the collar is achieved.
NOTE: All gas connections must be contained within the fi replace when complete.
1. Move the fi replace into position and secure to the fl oor through the 1/4" holes located at either side of the base.
2. The fi replace is designed to accept 3/8" gas supply line.
3. Connect the gas supply in accordance to local codes. In the absence thereof, install according to the
National Installation Code.
4. When fl exing any gas line, support the gas valve so that the lines are not bent
or kinked.
5. Check for gas leaks by brushing on a soap and water solution.
DO NOT USE OPEN FLAME.
Purge all gas lines with the glass door open. Assure that a continuous gas fl ow is at
the burner before closing the door.
CER TIFIED UNDER / HOMOLOGUE SELON LES NORMES: CSA 2.33-2002, ANSI Z21.88-2002 VENTED GAS FIREPLACE HEATER / FOYER DE CHAUFFAGE AU GAZ AVEC EVACUA TION
DIRECT VENT GAS FIREPLACE. APPROVED FOR BEDROOM, BATHROOM AND BED-SITTING ROOM INSTALLATION. SUITABLE FOR MOBILE HOME INSTALLATION IF INSTALLED IN ACCORDANCE WITH THE
CURRENT STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED MOBILE HOMES, IN CANADA OR IN THE UNITED STATES THE MANUFACTURED HOME CONTRUCTION AND SAFETY STANDARD, TITLE 24
CFR, PART 3280. WHEN THIS US STANDARD IS NOT APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED HOME INSTALLATIONS, SITES AND COMMUNITIES, ANSI / NFPA 501A.
FOYER A GAZ VENTILE DIRECT. HOMOLOGUE POUR INSTALLATION DANS UNE CHAMBRE A COUCHER, UNE SALLE DE BAIN ET UN STUDIO. APPROPRIE POUR INSTALLATION DANS UNE MAISON MOBILE
SI SON INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SERIE DE MAISONS MOBILES EQUIPEES AU GAZ, EN VIGUEUR AU CANADA OU AUX ETATS-UNIS DE LA NORME DE
SECURITE ET DE CONSTRUCTION DE MAISONS MANUFACTUREES, TITRE 24 CFR, SECTION 3280. DANS LE CAS OU CETTE NORME D'ETATS-UNIS NE PEUT ETRE APPLIQUEE, SE REFERER A LA NORME
RELATIVE AU CRITERE DE MESURES DE SECURITE CONTRE L'INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS MANUFACTURES, LES SITES ET LES COMMUNAUTES, ANSI/NFPA 501A.
MODEL BGD40 - N
ALTITUDE/ELEVATION:
INPUT/ALIMENTATION:
MODEL BCDV400 - N
REDUCED INPUT/ALIMENTA TION REDUIT:
ORIFICE:
MANIFOLD PRESSURE: 3.5" WATER COLUMN
PRESSION AU COLLECTEUR: 3.5" D'UNE COLONNE D'EAU
MINIMUM SUPPLY PRESSURE: 4.5" WATER COLUMN
PRESSION D'ALIMENTATION MINIMALE: 4.5" D'UNE COLONNE D'EAU
MAXIMUM SUPPLY PRESSURE: 7.0" WATER COLUMN
PRESSION D'ALIMENTA TION MAXIMAL: 7.0" D'UNE COLONNE D'EAU
NOT FOR USE WITH SOLID FUEL. FOR USE WITH COVERS AND
GLASS DOORS CERTIFIED WITH THIS UNIT ONLY.
WARNING:
DO NOT ADD ANY MATERIAL TO THE APPLIANCE, WHICH WILL COME IN CONTACT
WITH THE FLAMES, OTHER THAN THA T SUPPLIED BY THE MANUFACTURER WITH THE APPLIANCE.
MINIMUM CLEARANCE TO COMBUSTIBLE MA TERIALS /
DEGAGEMENTS MINIMAUX DES MA TERIAUX COMBUSTIBLES:
TOP, FLOOR, SIDES & BACK
DESSUS, PLANCHER, COTES & ARRIERE
RECESSED DEPTH (CORNER INSTALLATION ONL Y)
PROFONDEUR D'ENCASTRE (INSTALLATION DU COIN SEULEMENT)
VENT / EVENT
MANTLE HEIGHT / HAUTEUR DU MANTEAU
*
MAXIMUM HORIZONTAL EXTENSION / L'EXTENSION HORIZONTALE MAXIMALE: 3". SEE INSTRUC-
TION MANUAL FOR GREATER EXTENSIONS. REFERER AU MANUEL D'INSTRUCTION POUR DES
EXTENSIONS PLUS GRANDES.
MINIMUM AND MAXIMUM HORIZONTAL VENT LENGTHS ARE 10 INCHES AND 20 FEET RESPEC-
TIVELY. LES LONGUEURS HORIZONTALES MINIMALE ET MAXIMALE SONT 10 POUCES ET 20 PIEDS
RESPECTIVEMENT.
WOLF STEEL LTD, BARRIE, ON, CANADA
1. Install the 5" diameter fl ex pipe
to the fi replace. Secure with 3
screws and fl at washers. Seal
the joint and screw holes using
high temp sealant
(not supplied) or Red
RTV Silicone may
also be used in this
location.
2. Install the 8" diam-
eter fl ex pipe to the
fi replace. Attach and
FIGURE 40
seal the joints.
For optimum per-
formance it is recommended that all horizontal runs have a
¼" rise per foot.
GAS INSTALLATION
Proceed once the vent installation is complete.
0-4500FT(0-1370m)
30,000 BTU/h
20,000 BTU/h
#39
REFERENCE #15510
CERTIFIED FOR
CANADA AND
CERTIFIEE POUR
UN COMBUSTIBLE SOLIDE NE DOIT PAS ETRE UTILISE AVEC CET
APPAREIL. UTILISER AVEC LES COUVERTURES ET LES PORTES
VITREES HOMOLOGUEES SEULEMENT AVEC CETTE UNITE.
AVERTISSEMENT:
CONTACT AVEC LES FLAMMES AUTRE QUE CELUI QUI EST FOURNI AVEC CET APPAREIL PAR LE
FABRICANT.
THE APPLIANCE MUST BE VENTED USING THE APPROPRIATE WOLF STEEL VENT KITS. SEE OWNERS
0
INSTALLATION MANUAL FOR VENTING SPECIFICS. PROPER REINSTALLATION AND RESEALING IS
NECESSAR Y AFTER SER VICING THE VENT-AIR INTAKE SYSTEM.
25¼"
L'APPAREIL DOIT EVACUER SES GAZ EN UTILISANT L'ENSEMBLE D'EVACUA TION PROPRE A WOLF
STEEL. REFERER AU MANUEL D'INSTALLATION DE PROPRIETAIRE POUR L'EVACUA TION PRECISE. IL
EST IMPORTANT DE BIEN REINSTALLER ET RESCELLER L'EVENT APRES AVOIR ASSURE LE MAINTIEN
1"
DU SYSTEME DE PRISE D'AIR.
*
5"
ELECTRICAL RATING / CLASSIFICA TION: 115V, 0.82AMP , 60HZ
OPTIONAL FAN KIT / ENSEMBLE DE VENTILATEUR FACUL TATIF: GZ-550KT
MADE IN CANADA / FABRIQUE AU CANADA
SERIAL NUMBER/NO. DE SERIE:
GD22

FIREPLACE VENT CONNECTION

MANUAL SHUT-OFF VALVE
ALTITUDE / ELEVA TION:
0-4500FT (0-1370m)
INPUT /ALIMENTA TION:
30,000 BTU/h
REDUCED INPUT / ALIMENTA TION REDUIT:
20,000 BTU/h
ORIFICE:
#52
MANIFOLD PRESSURE: 10" WATER COLUMN
PRESSION AU COLLECTEUR: 10" D'UNE COLONNE D'EAU
MINIMUM SUPPLY PRESSURE: 11" WATER COLUMN
USA
PRESSION D'ALIMENTA TION MINIMALE: 11" D'UNE COLONNE D'EAU
ET
MAXIMUM SUPPLY PRESSURE: 13" WATER COLUMN
PRESSION D'ALIMENTA TION MAXIMAL: 13" D'UNE COLONNE D'EAU
N'AJOUTEZ P AS A CET APPAREIL AUCUN MA TERIAU DEVANT ENTRER EN
BGD40 / BCDV400
FIGURE 41
FIGURE 42
MODEL BGD40 - P
MODEL BCDV400 - P
W385-0249
FIGURE 42
W415-0299 / J / 04.14.08
21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bgd40-n

Table of Contents