Panasonic CS-E7PKR Service Manual page 101

Hide thumbs Also See for CS-E7PKR:
Table of Contents

Advertisement

14.1.4
Compressor Overheating Prevention Control
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The
changes of frequency are as below.
If compressor discharge temperature exceeds 103°C, compressor will be stopped, occurs 4 times per 20 minutes,
timer LED will be blinking. ("F97" is indicated.)
14.1.5
Low Pressure Prevention Control (Gas Leakage Detection)
Control start conditions
For 5 minutes, the compressor continuously operates and outdoor total current is between 0.75A and 0.95A
o
(E7/9/12/15PK), 1.38A and 1.65A (E18PK), 1.89A and 2.75A (E21PK), 1.88A and 2.85A (Cooling), 2.85A
and 3.57A (Heating) (E24/28PK).
During Cooling and Soft Dry operations:
o
Indoor suction temperature - indoor piping temperature is below 4°C.
During Heating operations :
o
Indoor piping temperature - indoor suction is under 5°C.
Control contents
Compressor stops (and restart after 3 minutes).
o
If the conditions above happen 2 times within 20 minutes, the unit will:
o
Stop operation
Timer LED blinks and "F91" indicated.
14.1.6
Low Frequency Protection Control 1
When the compressor operate at frequency lower than 24 Hz continued for 20 minutes, the operation frequency
will be changed to 23 Hz for 2 minutes.
14.1.7
Low Frequency Protection Control 2
When all the below conditions comply, the compressor frequency will change to lower frequency.
Indoor intake air (°C)
Outdoor air (°C)
Indoor heat exchanger (°C)
Temperature, T, for:
Cooling/Soft Dry
T < 14 or T ≥ 30
T < 13 or T ≥ 38
T < 30
101
Heating
T < 14 or T ≥ 28
T < 4 or T ≥ 24
T ≥ 0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents