Lennox G61MPV Service Manual page 61

G61mpv series units
Hide thumbs Also See for G61MPV:
Table of Contents

Advertisement

FIELD SUPPLIED WALL TERMINATION OR
(15F74) WALL RING TERMINATION KIT
With INTAKE ELBOW
NOTE − FIELD PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
TO TERMINATION
C
1/2" (13mm) ARMAFLEX INSULATION
IN UNCONDITIONED SPACE
E
* WALL
SUPPORT
C
See venting table 37 for maximum venting lengths with this
arrangement.
* Use wall support every 24" (610 mm). Use two wall supports if
extension is greater than 24" (610 mm) but less than 48" (1219 mm).
NOTE − One wall support must be 6" (152 mm) from top of each pipe
(intake and exhaust)
2" (51mm)
Vent Pipe
A−Minimum clearance
12" (508MM)
above grade or average
snow accumulation
B−Maximum horizontal
6" (152MM)
separation between
intake and exhaust
C−Minimum from
end of exhaust to
6" (152MM)
inlet of intake
D−Maximum exhaust
12" (305MM)
pipe length
E−Maximum wall support
6" (152MM)
distance from top of each
pipe (intake/exhaust)
FIGURE 34
1/2" (13mm) ARMAFLEX
INSULATION IN UN-
CONDITIONED SPACE
SIZE TERMINATION
PER TABLE 38
D
B
STRAIGHT
APPPLICATION
A
D
B
A
EXTENDED
APPLICATION
3" (76mm)
Vent Pipe
12" (508MM)
6" (152MM)
6" (152MM)
20" (508MM)
6" (152MM)
EXHAUST PIPE TERMINATION SIZE REDUCTION
G61MPV
MODEL
045, 070, 071
090, 091
110, 111
135
5. On field supplied terminations for side wall exit, ex-
haust piping may extend a maximum of 12 inches
(305mm) for 2" PVC and 20 inches (508mm) for 3"
(76mm) PVC beyond the outside wall. Intake piping
should be as short as possible. See figures 33 and 34.
6. On field supplied terminations, a minimum distance
between the end of the exhaust pipe and the end of
the intake pipe without a termination elbow is 8" and a
minimum distance of 6" with a termination elbow. See
figures 33 and 34.
7. If intake and exhaust piping must be run up a side wall
to position above snow accumulation or other ob-
structions, piping must be supported every 24"
(610mm) as shown in figures 33 and 34. In addition,
close coupled wall termination kits must be extended
for use in this application. See figures 40 and 41.
When exhaust and intake piping must be run up an
outside wall, the exhaust piping must be terminated
with pipe sized per table 38.The intake piping may be
equipped with a 90° elbow turndown. Using turndown
will add 5 feet (1.5m) to the equivalent length of the
pipe.
8. Based on the recommendation of the manufacturer, a
multiple furnace installation may use a group of up to
four terminations assembled together horizontally, as
shown in figure 37.
Page 61
TABLE 38
Exhaust Pipe Size
2" (51mm), 2−1/2" (64mm),
3" (76mm) or 4" (102mm)
3" (76mm) or 4" (102mm)
Termination
Pipe Size
1−1/2" (38mm)
2" (51mm)
2" (51mm)
2" (51mm)