BLOWER DATA
G61MPV−60C−091 BLOWER PERFORMANCE (less filter)
Side Return Air with Optional RAB Return Air Base
0 through 1.00 in. w.g. External Static Pressure Range
ADJUST"
Switch
Positions
+
1
NORM
ADJUST"
Switch
Positions
+
1
NORM
1
Factory default jumper setting.
N/A − First and second stage HEAT positions shown cannot be used on this model.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT speed position.
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 458 cfm.
G61MPV−60C−091 BLOWER MOTOR WATTS
Jumper Speed
Positions
0
0.1
+" (Plus) SETTING ( Adjust" Jumper at +" Setting)
HEAT"
Tap 1 210
235
Speed
Tap 2 270
300
Tap 3 430
455
Tap 4 525
560
COOL"
Tap 1 145
165
Speed
Tap 2 175
195
Tap 3 230
260
Tap 4 335
365
NORM" (Normal) SETTING ( Adjust" Jumper at NORM" Setting)
HEAT"
Tap 1 160
185
Speed
Tap 2 205
235
Tap 3 325
350
Tap 4 410
445
COOL"
Tap 1 105
125
Speed
Tap 2 135
155
Tap 3 175
200
Tap 4 235
260
−" (Minus) SETTING ( Adjust" Jumper at −" Setting)
HEAT"
Tap 1 120
140
Speed
Tap 2 145
170
Tap 3 230
255
Tap 4 280
315
COOL"
Tap 1 85
100
Speed
Tap 2 100
120
Tap 3 140
155
Tap 4 180
205
Second Stage HEAT" Speed − cfm
1
1
2
1490
1690
1345
1520
1195
1345
First Stage HEAT" Speed − cfm
1
1
2
1360
1550
1225
1400
1100
1225
Motor Watts @ Various External Static Pressures − in. wg.
First Stage
0.2
0.3
0.4
0.5
0.6
265
295
325
350
380
340
380
415
450
485
490
520
550
580
610
600
635
675
710
750
185
210
230
255
275
220
245
270
290
315
285
315
345
370
395
390
415
445
470
500
210
235
260
280
305
265
295
330
355
385
375
400
430
455
475
475
510
545
575
605
150
170
195
220
240
180
200
225
240
260
225
250
275
305
330
290
320
350
375
405
165
190
215
235
260
200
225
255
285
315
285
315
345
370
395
350
385
420
450
480
120
140
160
180
195
145
165
190
210
230
180
200
225
245
265
230
255
280
305
330
Speed Switch Positions
3
4
1
1850
2050
1590
1700
1870
1445
1525
1675
1280
3
4
1
1720
1880
1125
1540
1715
1030
1385
1540
915
0.7
0.8
0
0.1
405
435
265
295
520
555
355
395
645
675
530
656
790
825
680
725
295
315
353
380
335
360
445
475
420
450
640
680
525
560
855
885
325
355
195
225
415
450
250
285
500
530
415
445
640
670
505
545
261
280
260
285
275
300
320
350
360
375
475
515
430
460
625
665
285
305
150
170
345
370
185
210
420
445
310
335
515
540
385
415
215
235
195
220
250
265
235
260
285
305
375
400
355
380
450
480
Page 12
Second Stage COOL" Speed − cfm
2
3
1695
1905
1535
1740
1370
1580
First Stage COOL" Speed − cfm
2
3
1195
1370
1085
1230
980
1110
Second Stage
0.2
0.3
0.4
0.5
0.6
330
365
400
425
450
445
490
535
570
610
600
640
675
700
730
775
820
870
905
935
410
440
470
500
530
510
540
575
600
625
725
765
810
840
870
915
940
970
970
965
255
285
320
345
365
325
365
405
435
465
475
505
540
570
605
585
625
660
700
740
315
345
375
400
420
385
420
455
480
505
555
595
635
665
695
705
750
790
815
840
195
220
245
270
295
240
270
305
330
360
365
390
415
445
470
445
480
515
545
580
245
270
295
315
335
290
320
345
370
395
430
455
485
520
555
515
545
580
610
645
1
4
2035
1900
1700
1
4
1530
1380
1225
0.7
0.8
480
500
645
675
755
775
970
995
555
580
650
675
905
890
965
935
390
420
495
530
635
665
780
815
445
475
530
565
730
760
865
855
320
345
390
425
495
520
610
640
360
385
420
455
590
620
675
705

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents