Air For Combustion And Ventilation - Superior SVYD18NRA Installation And Operation Instructions Manual

Unvented (vent-free) gas stove heater, remote-ready control gas log heater (burner system for cast iron stove)
Table of Contents

Advertisement

WARNING: This heater shall not be installed in a
room or space unless the required volume of indoor
combustion air is provided by the method described
in the National Fuel Gas Code, ANSI Z223.1/NFPA 54,
the International Fuel Gas Code, or applicable local
codes. Read the following instructions to insure proper
fresh air for this and other fuel-burning appliances in
your home.
Today's homes are built more energy efficient than ever. New materi-
als, increased insulation and new construction methods help reduce
heat loss in homes. Home owners weather strip and caulk around
windows and doors to keep the cold air out and the warm air in.
During heating months, home owners want their homes as airtight
as possible.
While it is good to make your home energy efficient, your home needs
to breathe. Fresh air must enter your home. All fuel-burning appliances
need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers and fuel burning appliances
draw air from the house to operate. You must provide adequate fresh
air for these appliances. This will insure proper venting of vented fuel-
burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/
NFPA 54, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation
classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space
The information on pages 5 through 6 will help you classify your
space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough
fresh air for combustion and ventilation. However, in buildings of
unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a. walls and ceilings exposed to the outside atmosphere have a
continuous water vapor retarder with a rating of one perm (6 x
10
kg per pa-sec-m
) or less with openings gasketed or sealed
-11
2
and
b. weather stripping has been added on openable windows and
doors and
c. caulking or sealants are applied to areas such as joints around
window and door frames, between sole plates and floors, be-
tween wall-ceiling joints, between wall panels, at penetrations
for plumbing, electrical and gas lines and at other openings.
If your home meets all of these three criteria, you must provide ad-
ditional fresh air. See Ventilation Air From Outdoors, page 6.
If your home does not meet all of the three criteria above, proceed
to Determining Fresh-Air Flow For Fireplace Location.
127113-01A

AIR FOR COMBUSTION AND VENTILATION

Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined
space as a space whose volume is less than 50 cubic feet per 1,000
Btu/hr (4.8 m
installed in that space and an unconfined space as a space whose
volume is not less than 50 cubic feet per 1,000 Btu/hr (4.8 m
kw) of the aggregate input rating of all appliances installed in that
space. Rooms communicating directly with the space in which the
appliances are installed*, through openings not furnished with doors,
are considered a part of the unconfined space.
* Adjoining rooms are communicating only if there are doorless
passageways or ventilation grills between them.
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or uncon-
fined space.
Space: Includes the room in which you will install fireplace plus any
adjoining rooms with doorless passageways or ventilation grills
between the rooms.
1. Determine the volume of the space (length x width x height).
2. Multiply the space volume by 20 to determine the maximum Btu/
3. Add the Btu/Hr of all fuel burning appliances in the space.
4. Compare the maximum Btu/Hr the space can support with the
www.Superiorfireplaces.US.com
per kw) of the aggregate input rating of all appliances
3
Length x Width x Height =__________cu. ft. (volume of space)
Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling
height) = 2560 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills
or openings, add the volume of these rooms to the total volume
of the space.
Hr the space can support.
_______ (volume of space) x 20 = (Maximum Btu/Hr the space
can support)
Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum
Btu/Hr the space can support)
Vent-free fireplace
Gas water heater*
Gas furnace
Vented gas heater
Gas fireplace logs
Other gas appliances* +
Total
=
* Do not include direct-vent gas appliances. Direct-vent draws
combustion air from the outdoors and vents to the outdoors.
Example:
Gas water heater
40,000 Btu/Hr
Vent-free fireplace + 30,000 Btu/Hr
Total
= 70,000 Btu/Hr
actual amount of Btu/Hr used.
______ Btu/Hr (maximum the space can support)
______ Btu/Hr (actual amount of Btu/Hr used)
Example: 51,200 Btu/Hr (maximum the space can support)
70,000 Btu/Hr (actual amount of Btu/Hr used)
per
3
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
5