Central Remote Controller; Operation For Check Display - Toshiba RAV-SM560AT-E Service Manual

Air conditioner split type
Hide thumbs Also See for RAV-SM560AT-E:
Table of Contents

Advertisement

14-2-3. Central remote controller

1. Operation for CHECK display

When pushing the CHECK switch, the indoor unit No. (Network address No.) including the check data is
displayed in the UNIT No. display section, and the check code is displayed in the set up temp. display sec-
tion.
MONITOR
ZONE
ON
UNIT
SET
ALL
OFF
1
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
MONITOR/SET ALL/ZONE
ZONE
UNIT
ON CENTER/LOCKED
ZONE SET/ENTER SELECT
OFF
2. Reading of CHECK monitor display
<7 segment display>
0
1
2
3
<Display on CHECK monitor>
Unit line No. (Network address No.)
MONITOR
ZONE
SET
ALL
1
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
Check code detected at first
Check code detected at last
<CHECK data>
(Example)
In No.1 unit, first the interconnection wire (bus communication line) of indoor/outdoor has failed.
Next, the room temp. sensor is defective.
For No.16 unit, the high pressure switch at the inverter unit side operates.
UNIT
ON
CENTER
AUX. TYPE
STANDBY
LOCKED
TIMER No.
FILTER
MODE
FAN
TEMP . CHECK
FAN ONLY
AUTO
1
˚C
COOL
HIGH
2
DRY
MED.
LOUVER
HEAT
LOW
AUTO
FIX
MANUAL
MODE
TEMP.
FILTER RESET
CHECK
TIMER ON
FAN
LOUVER
4
5
6
7
ON
CENTER
UNIT
OFF
LOCKED
MODE
FAN ONLY
COOL
HEAT
AUTO
UNIT
TEMP . CHECK
1
CHECK switch
Push for 0.5 seconds to display CHECK code.
Push for 3 seconds to reset indoor microprocessor.
(While indoor microprocessor is locked by ALL STOP alarm)
Push for 10 seconds to clear check data.
RESET switch
8
9
10
11
AUX. TYPE
STANDBY
TIMER No.
FILTER
FAN
TEMP . CHECK
AUTO
1
˚C
HIGH
2
DRY
MED.
LOUVER
LOW
FIX
MANUAL
TEMP . CHECK
2
– 117 –
Push the switch in the hole with pin.
The remote controller resets initialized.
(All data is cleared.)
12
13
14
15
(Example)
There is no check data.
UNIT
UNIT
Hexadecimal
notation
Decimal notation
TEMP . CHECK
TEMP . CHECK
1