Set Temperature Rise - Carrier 58TUA Installation, Start-Up, And Operating Instructions Manual

2-speed, 2-stage induced-combustion gas furnace size 040-135, series 110 or 120
Table of Contents

Advertisement

Table 10—Gas Rate (Cu Ft/Hr)
SIZE OF TEST DIAL
SECONDS
FOR 1
1
2
REVOLUTION
cu ft
cu ft
cu ft
10
360
720
1800
11
327
655
1636
12
300
600
1500
13
277
555
1385
14
257
514
1286
15
240
480
1200
16
225
450
1125
17
212
424
1059
18
200
400
1000
19
189
379
947
20
180
360
900
21
171
343
857
22
164
327
818
23
157
313
783
24
150
300
750
25
144
288
720
26
138
277
692
27
133
267
667
28
129
257
643
29
124
248
621
30
120
240
600
31
116
232
581
32
113
225
563
33
109
218
545
34
106
212
529
35
103
206
514
36
100
200
500
37
97
195
486
38
95
189
474
39
92
185
462
40
90
180
450
41
88
176
439
42
86
172
429
43
84
167
419
44
82
164
409
45
80
160
400
46
78
157
391
47
76
153
383
48
75
150
375
49
73
147
367
EXAMPLE: (High-heat operation at 0—2000 ft altitude)
Furnace input from rating plate is 85,000 Btuh
Btu heating input = Btu/cu ft X cu ft/hr
Heating value of gas = 1050 Btu/cu ft
Time for 1 revolution of 2-cu ft dial = 92 sec
Gas rate = 80 cu ft/hr (from Table 10)
Btu heating input = 80 X 1050 = 84,000 Btuh In this
example, the orifice size and manifold pressure adjustment
is within ±2 percent of the furnace input rate.
NOTE: Measured gas inputs (high heat and low heat) must be
within ±2 percent of that stated on furnace rating plate when
installed at sea level or derated per that stated above when installed
at higher altitudes.
m. Remove jumper across R, W/W1, and W2 thermostat
connections to terminate call for heat.

5. Set temperature rise.

Place SW-2 in ON position. Jumper R to W/W1 and W2 to
check high-gas-heat temperature rise. To check low-gas-heat
temperature rise, remove jumper to W2. Determine air tem-
perature rise for both high and low fire. Do not exceed
temperature rise ranges specified on unit rating plate for high
and low fire.
a. Place duct thermometers in return and supply ducts as near
furnace as possible. Be sure thermometers do not see heat
SIZE OF TEST DIAL
SECONDS
FOR 1
5
1
2
REVOLUTION
cu ft
cu ft
50
72
144
51
71
141
52
69
138
53
68
136
54
67
133
55
65
131
56
64
129
57
63
126
58
62
124
59
61
122
60
60
120
62
58
116
64
56
112
66
54
109
68
53
106
70
51
103
72
50
100
74
48
97
76
47
95
78
46
92
80
45
90
82
44
88
84
43
86
86
42
84
88
41
82
90
40
80
92
39
78
94
38
76
96
38
75
98
37
74
100
36
72
102
35
71
104
35
69
106
34
68
108
33
67
110
33
65
112
32
64
116
31
62
120
30
60
exchangers so that radiant heat will not affect thermometer
readings. This is particularly important with straight run
ducts.
5
cu ft
360
355
346
340
333
327
321
316
INLET
310
PRESSURE
305
TAP
300
290
281
273
265
257
250
243
237
231
225
220
214
209
205
200
196
192
188
184
180
Fig. 14—Redundant Automatic
178
173
170
167
BURNER FLAME
164
161
155
150
MANIFOLD
b. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine tem-
perature rise.
NOTE: If the temperature rise is outside this range, first check:
(1.) Gas input for low- and high-fire operation.
(2.) Derate for altitude if applicable.
(3.) Return and supply ducts for excessive restrictions
causing static pressures greater than 0.50-in. wc.
c. Adjust air temperature rise by adjusting blower speed.
Increase blower speed to reduce temperature rise. Decrease
blower speed to increase temperature rise. For high fire,
speed selection can be med-high, med (5-speed blowers
only), or med-low (factory setting). For low fire, speed
selection can be low (factory setting), med-low, or med
(5-speed blowers only).
20
ON/OFF
SWITCH
MANIFOLD
PRESSURE
TAP
Gas Control Valve
Fig. 15—Burner Flame
LOW-FIRE
ADJUSTMENT
ALLEN SCREW
(UNDER CAP)
HIGH-FIRE
ADJUSTMENT
ALLEN SCREW
(UNDER CAP)
A97358
BURNER
A89020

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents