Low Ambient Damper
Installation
Reference Figure I-IP-2 and follow the
procedure below to install the low
ambient damper option.
1. Using a 1" hole saw, make a hole on
the right side of the condenser fan
discharge panel as shown. Install a 1"
bushing into the hole.
SELF-DRILLING SCREW 3/16" X 5/8"
Figure I-IP-2. Low ambinet damper installation
16
Installation
2. Apply the soft gasket material provided
around the damper as shown.
3. Place the damper over the discharge
opening using the screws (
provided. See Detail A.
4. Install the damper actuator, which was
previously assembled to the mounting
bracket, to the right panel of the
damper using the four screws (
PROVIDED
SOFT GASKET
PROVIDED
DETAIL "A"
3
5
/
x
/
")
16
8
1
/
x
5
/
")
4
8
CONDENSER FAN DISCHARGE PANEL
1" HOLE
(FIELD OPERATION)
Installation
Procedure
provided. Be sure the damper actuator
is in the closed position when installing.
5. Connect the capillary tube to the
pressure operator using the flare fitting.
Insert the tube through bushing
referenced in step 1. Route the capillary
tube to the liquid line on circuit #1.
6. Remove the end cap from the access
valve and attach to the end of the
capillary tube.
LIQUID LINE CIRCUIT #1