The heat pump and collector hose in general

The heat pump and collector hose in general

Transporting the heat pump

The heat pump should always be transported and stored in an upright position.
Otherwise the suspension fi ttings inside the compressor can be damaged. If the
heat pump must be tilted during entry to the installation site, this should be done
for as short a time as possible. The outer cover plates should be removed to avoid
damage, if the heat pump is moved without using the supplied pallet.
The heat pump must not be stored at temperatures below -10ºC.

Positioning the heat pump

It is important that the heat pump stands on a fl at surface as it contains sensitive
parts. Adjust the rubber feet so the heat pump does not lean.
The temperature surrounding the heat pump must be between 0ºC and 35ºC.
The installer should take sound propagation into consideration when positioning the
heat pump.
Make sure there is a fl oor drain in the room where the heat pump is installed. The
fl oor drain ensures any water is easily transported away if leakage should occur.

Maximum working temperatures

The heat pump can work at a maximum return water temperature of approximately
57ºC. If the temperature rises above this value the heat pump will stop for reasons of
safety.
The maximum outgoing temperature to the heating system is around 65°C.
However, even higher temperature can be attained with the help of the immersion
heater.
Fit the particle fi lter
The task of the particle fi lter is to fi lter out dirt before it can enter the heat pump.
Accordingly, the supplied particle fi lters should always be fi tted on the incoming
pipes on both the hot and cold sides. The fi lters should be fi tted as close to the heat
pump as possible and placed horizontally.
Two particle fi lters are supplied with Greenline HT Plus C. These are to be fi tted on
the outside of the heat pump. On Greenline HT Plus E the particle fi lter for the hot
side is already fi tted inside the heat pump. The supplied fi lter is to be fi tted on the
cold side, outside of the heat pump.
44