Air To Air Heat Pump Operation In Thermistor Error - IVT 09LR-N Service Manual

Split type air to air heat pump
Table of Contents

Advertisement

Function
29 PAM clock error
When power source frequency can-
not be determined (at startup), or
when power source clock cannot
be detected for 1 continuous sec-
ond (at startup).
✩1—The outdoor unit restarts four times before the indoor unit error is displayed (complete shutdown).
✩2—A single error judgment results in the display of the indoor unit error (complete shutdown).
✩3—The outdoor unit restarts eight times before the indoor unit error is displayed (complete shutdown).

[2] AIR TO AIR HEAT PUMP OPERATION IN THERMISTOR ERROR

1. Indoor unit
Item
Mode
Room temperature
Auto
thermistor (TH1)
Cooling
Dehumidifying
Heating
Heat exchanger
Cooling
thermistor (TH2)
Dehumidifying
Heating
Operation
Description
Detection period
At compressor startup,
when in operation
Control operation When resistance
is low (tempera-
ture judged higher
than actual)
Operation mode
Cooling mode is
judgment
activated even if
room temperature
is low.
Frequency control Room becomes too
cold.
Room temperature
Normal operation.
memory
Frequency control
Frequency control Room does not
become warm.
Freeze prevention Indoor unit evapo-
rator may freeze.
Cold air prevention Cold air prevention
deactivates too
soon and cold air
discharges.
Reset condition
Compressor continues
operation without stop-
ping.
Short-circuit
Cooling mode is
Heating mode is
activated in most
activated even if
cases.
room temperature
is high.
Air conditioner
Room does not
operates in full
become cool.
power even when
set temperature is
reached.
Room temperature
Normal operation.
is stored in memory
as 31.0C, and
compressor does
not stop.
Hot keep status
Room becomes too
results immedi-
warm.
ately after opera-
tion starts.
Frequency does
not increase above
30 Hz (40 Hz).
Indoor unit evapo-
Compressor stops
rator may freeze.
occasionally.
Compressor oper-
Cold air prevention
ates at low speed
deactivates too
or stops, and fre-
slow.
quency does not
increase.
3 – 3
Self-diagnosis result
display
Indoor
Indoor
unit error
unit
display
None
Yes
When resistance
Open-circuit
is high (tempera-
ture judged lower
than actual)
Heating mode is
always activated.
Compressor does
not operate.
Room temperature
is stored in memory
as 18.5C, and
compressor does
not operate.
Air conditioner
operates in full
power even when
set temperature is
reached.
Compressor does
not operate.
Cold air prevention
does not deacti-
vate, and indoor
unit fan does not
rotate.
12LRN
Outdoor
unit
Yes