Electric Element Fault; Heat Pump Now Working At Max. Permitted Temp. (T8); Electric Element Now Working At Max; Permitted Temp. (T8) - IVT X Series Manual

Fault tracing tree
Table of Contents

Advertisement

Rectify interference

2.3.12 Electric element fault

6 720 643 196-10.1I
Description: Electric element fault Reset on the overheat protection and must be acknowledged in the display.
Check
1.
B Check the supply to the electrical
additional heat (measured on the AHB
circuit board terminals).
Is it OK?
2.
B Try to reset the overheat protection
again.
Was it successful?
3.
Overheat protection electric element
defective.
Tab. 12
2.3.13 Heat pump now working at max. permitted
temp. (T8)
Description: Value on T8 has exceeded 65 °C.
6 720 643 196-11.1I
See fault tracing tree High forward flow
T1. (
Chapter 2.3.5)
Tab. 13
2.3.14 Electric element now working at max. permit-
ted temp. (T8)
Description: Value on T8 has exceeded 75 °C.
6 720 643 196-12.1I
See fault tracing tree High forward flow
T1. (
Chapter 2.3.5)
Tab. 14
18
Action
yes:
2
no:
B Check the wiring in the heat pump.
yes:
Does the error message recur?
no:
3
B Replace the AHB board.
(Can only occur during additional heat operation).
3
6 720 643 196 (2010/02)