Download Print this page

Carrier AQUAZONE 50PSW036-360 Installation And Service Instructions Manual page 17

Water-to-water source heat pump with puron refrigerant (r-410a)
Hide thumbs Also See for AQUAZONE 50PSW036-360:

Advertisement

Deluxe
D Control
Accessory
Relay Configura-
tions (See Tables 4 and 5) -- The
following
acces-
sory relay settings are applicable
for Deluxe D control only:
CYCLE
WITH COMPRESSOR
-- In this configuration,
the
relay will be ON any time the compressor
relay is on.
DIGITAL
NIGHT
SETBACK
(NSB) -- In this
configura-
tion, the relay will be ON if the NSB input is connected
to
ground C.
NOTE: If there are no relays configured
for digital NSB, then
the NSB
and OVR inputs
are automatically
configured
for
mechanical
operation.
MECHANICAL
NIGHT
SETBACK
-- When NSB input is
connected
to ground C, all thermostat
inputs are ignored.
A
thermostat
setback heating call will then be connected
to the
OVR input. If OVR input becomes active, then the Deluxe D
control will enter night low limit (NLL) staged heating mode.
The NLL staged heating mode will then provide heating during
the NSB period.
WATER VALVE (SLOW
OPEN1NG)
-- If relay is config-
ured for water valve (slow opening), the relay will start 60 sec-
onds prior to starting compressor
relay.
To avoid equipment
damage, DO NOT leave system filled
in a building without
heat during the winter unless
anti-
freeze
is added to system
water. Condenser
coils never
fully drain by themselves
and will freeze unless winterized
with antifreeze.
Table 4 -- DIP Switch Block $2 --
Accessory 1 Relay Options
ACCESSORY
1
DIP SWITCH POSITION
RELAY OPTIONS
1
2
3
Digital NSB
Off
On
On
Water Valve -- Slow Opening
On
Off
On
LEGEND
NSB --
Night Setback
NOTE: All other DIP switch combinations
are invalid,
Table 5 -- DIP Switch Block $2 --
Accessory 2 Relay Options
ACCESSORY
2
DIP SWITCH POSITION
RELAY OPTIONS
4
5
6
Digital NSB
Off
On
On
Water Valve -- Slow Opening
On
Off
On
LEGEND
NSB --
Night Setback
NOTE: All other DIP switch combinations
are invalid,
START-UP
Use the procedure outlined below to initiate proper unit
start-up.
NOTE: This equipment is designed for indoor installation
only.
Operating
Limits (See Table 6)
ENVIRONMENT-
This equipment
is designed
for indoor
installation
ONLY. Extreme variations
in temperature,
humidi-
ty and corrosive water or air will adversely affect the unit per-
formance, reliability
and service life.
POWER
SUPPLY-
A voltage variation
of+
10% of name-
plate utilization
voltage is acceptable.
UNIT STARTING
CONDITIONS
-- All units start and op-
erate in an ambient of 45 F with entering air at 40 F and enter-
ing water at 20 F.
NOTE: These operating
conditions
are not normal or continu-
ous operating
conditions.
It is assumed
that start-up is for the
purpose
of bringing
the building
space
up to occupancy
temperature.
When
the disconnect
switch
is closed,
high voltage
is
present in some areas of the electrical panel. Exercise
cau-
tion when working with the energized equipment.
Table 6 -- 50PSW
Unit Operating
Limits
WATER LIMITS
COOLING
HEATING
(F)
(F)
SOURCE COIL
Min Entering Water
50
20
Normal Entering Water
85
60
Max Entering Water
110
70
LOAD COIL
Min Entering Water
50
60
Normal Entering Water
60
100
Max Entering Water
90
120
Unit Start-Up
1. Turn off all power to unit.
2. Adjust all valves to full open position.
3. Restore power to unit.
4. Operate
each unit in the cooling
cycle. See Table 6 for
unit entering water temperatures.
5. Operate each heat pump in the heating cycle ilranediately
after checking cooling cycle operation.
NOTE:
A time delay will prevent the compressor
from
re-starting
for approximately
5 minutes.
The time delay
function
can be ovemdden
on the Complete
C control
board.
6. If unit fails to operate, perform the following system
checks:
a.
Check
the voltage
and current. Be sure they com-
ply with electrical
data on unit nameplate.
b. Check
for loose terminal
screws
where
wire con-
nections
have been made on both the line and low-
voltage
terminal
boards.
c.
Check
the supply
and return
piping.
Be sure they
are properly
connected
to the inlet and outlet con-
nections
on the unit.
d.
If the checks
described
above
fail to reveal
the
problem
and the unit still will not operate,
contact
a trained
service
technician
to
ensure
proper
diagnosis.
Scroll Compressor
Rotation
--
It is important
to be
certain
compressor
is rotating
in the proper
direction.
To
determine
whether or not compressor
is rotating in the proper
direction:
1. Connect service gages to suction and discharge pressure
fittings.
2. Energize the compressor.
3. The
suction
pressure
should
drop and the discharge
pressure should rise, as is normal on any start-up.
17

Advertisement

loading