Carrier AQUAZONE 50PSW036-360 Installation And Service Instructions Manual page 15

Water-to-water source heat pump with puron refrigerant (r-410a)
Hide thumbs Also See for AQUAZONE 50PSW036-360:

Advertisement

L_ _r
k rx_%,
1
Contactor
-CCl
Contactor
-CC2
Grnd
Po_%_g,b,.,on
Tran_f
......
]
_2
_c
33
C Control
#1
g_
_o
[
J
C Control #2
Fig. 12 -- Typical Field Wiring
SUPPLY VOLTAGE-
Operating
voltage
to unit must
be
within voltage range indicated on unit nameplate.
Voltages
between
phases
must
be balanced
within
2%.
Use the following
formula to determine the percentage
voltage
imbalance:
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 460-3-60.
A
B
C
AB = 452-v
BC = 464-v
AC = 455-v
Average Voltage =
452 + 464 + 455
3
1371
3
=
457
Determine maximum
deviation from average voltage:
(AB) 457 - 452 = 5-v
(BC) 464 - 457 = 7-v
(AC) 457 - 455 = 2-v
Maximum
deviation is 7-v.
Determine percent voltage hnbalance.
7
% Voltage hnbalance = 100 x 45----5-
= 1.53%
This amount
of phase
hnbalance
is satisfactory
as it is
below the maximum
allowable 2%.
Operation
on hnproper
line voltage
or excessive
phase
imbalance
constitutes
abuse and may cause damage to electri-
cal components.
NOTE: If more than 2% voltage imbalance
is present, contact
local electric utility.
EXTERNAL
LOOP POWER
CONNECTION
-- If the unit
is to be connected
to an external loop pump or flow controller,
connect the pump to the loop pump terminal
block PB1. The
maxilnum
power handling is 4 amps at 240-v. The pumps will
automatically
cycle as required by the unit.
208-V OPERATION--All
208/240-v
units
are
factory
wired for 208-v. The transformers
may be switched
to 240-v
operation
(as illustrated
on the wiring diagram)
by switching
the red (208-v) wire with the orange (240-v) wire at the L2
terminal.
460-VOLT
OPERATION--Units
using
460-v
and internal
secondary
pump will require a neutral wire from the supply
side in order to feed accessory with 265-v.
Step 7 -- Wire Low Voltage
Connections
THERMOSTAT
CONNECTIONS
The thermostat
should
be wired
directly to the Aquazone
TM
control board. See Fig. 4-9.
WATER FREEZE
PROTECTION
-- The Aquazone
control
allows
the field selection
of source
fluid freeze
protection
points through jumpers.
The factory setting
of julnper
JW3
(FP1) is set for water at 30 E In earth loop applications,
julnper
JW3 should be clipped to change the setting to 10 F when
using antifreeze in colder earth loop applications.
See Fig. 13.
)
BR
BRG
CCG
CC
Clip JW3
protection
s,_ _
_:P_,
Lo*T,,_
Clip
for dry
contact
O
Y
©
P2
12
©
P3
=gg
©
Fig. 13 _ Typical Aquazone Control Board
Jumper Locations (Complete
C Control Shown)
ACCESSORY
CONNECTIONS-
The terminal
labeled
A
on the control is provided to control accessory
devices such as
water valves, electronic
air cleaners, humidifiers,
etc. This sig-
nal operates with the compressor
terminal.
See Fig. 14. Refer
to the specific unit wiring schematic for details.
Terminal Strip
{C)v
+
v
Typical
Water
Valve
Fig. 14 -- Typical Aquazone Accessory Wiring
(Deluxe D Control Shown)
NOTE: The A terminal should only be used with 24-v signals,
not line voltage signals.
IMPORTANT:
Two-compressor
units with Complete
C or
Deluxe D controls wired to terminal A will be turned off if
the controls are in lockout mode, even if the other board is
in normal operating mode.
15