Table 3A - Troubleshooting Chart - No Display - Lochinvar 50 Service Manual

Knight wall mount boiler
Table of Contents

Advertisement

3
Troubleshooting
Table 3A Troubleshooting Chart - No Display
FAULT
- No 120 vac supplied to unit.
No Display
- No voltage through the switch.
- Bad display board.
- Bad main control board.
- Blown fuse.
- Main control board temperature set point
satisfied.
- Remote thermostat satisfied.
No Burner
- Outside air temperature above Warm
Operation
Weather Shutdown (WWSD) set point for
main control board.
- Unit locked out on fault.
- Ramp delay active.
Unit Does Not
- Boiler controlled by BMS.
Modulate
Above 50%
- Flue sensor open.
(continued)
CAUSE
CORRECTIVE ACTION
• Check external line switch, fuse, or breaker.
• Check position of ON/OFF switch. Turn switch to the
ON position.
• Check 120 vac through the ON/OFF switch.
• Check wiring harness connection between display
board
and
main
control
harness at both points.
• Replace switch.
• Replace board.
• Replace the main control board.
• Replace fuse F3 on the main control board, see
page 28 of this manual.
• Review temperature setting.
• Review remote thermostat setting.
• Check location of outside air sensor.
resistance of outdoor air sensor and compare to Table
3D on page 30 of this manual.
• Consult display for specific fault.
descriptions on page 32 of this manual for corrective
actions.
• Check ramp delay parameter settings. Optional PC
software required.
• Turn ramp delay feature off. See page 20 of this
manual for instructions on how to turn this feature off.
• Check BMS parameter settings.
software required.
• Verify that the flue sensor is located in the flue outlet.
• Check wiring connections at the flue sensor.
• Check the resistance of the flue sensor and compare
to Table 3C on page 30 of this manual.
Service Manual
board.
Connect
Check
Refer to fault
Optional PC
29