Rheem RGFE Installation Instructions Manual page 77

Dedicated horizontal high efficiency modulating condensing gas furnace
Table of Contents

Advertisement

FIGURE 75b
MENU TREE – CONTINUED
TOTAL DAYS PWRD
MOD HT HRS
MOD HT CYCLS
BLOWER HRS
BLOWER CYCLES
®
4. IDM OUTPUT – Indicates the state
of the Induced Draft Motor (IDM) –
OFF, HI or LO. The indication is
the state at which the furnace con-
trol expects the motor to be. If the
indication is HI or LO and the motor
is not turning, a number of prob-
lems could be the cause – including
a non-functioning blower relay on
the furnace control or a non func-
tioning inducer.
5. FURN LO PR SW – Indicates the
state of the Low Pressure Control
(LPC) (also known as low pressure
switch) – either OPEN or CLOSED.
®
®
6. FURN HI PR SW – Indicates the
state of the High Pressure Control
(HPC) (also known as high pres-
sure switch) – either OPEN or
CLOSED.
7. GAS VLV PRCNT – Indicates the
firing rate of the modulating gas
valve. This value can be any num-
ber between 40% and 100%
depending on the thermostat
demand.
8. GAS VLV RELAY – Indicates the
state of the gas valve relay –either
ON or OFF. ON indicates that the
NOTE: There may be a
®
delay of several seconds
when accessing user
menus or submenus.
This is normal.
main gas valve solenoid is
engaged. Any time the indica-
tion is ON, flame should be pre-
sent.
9. FLAME – Indicates the pres-
ence of a flame. The possibili-
ties are "OFF", "MARGINAL",
"GOOD" and "UNEXPECTED".
A marginal flame can be an indi-
cator that the flame sense rod
needs to be cleaned. "UNEX-
PECTED" flame is a serious
condition and must be dealt with
immediately by a professional,
licensed HVAC technician.
77