INSTALLATION

BOILER ROOM

Important
• Keep vents free at all times.
• Do not store inflammable products in the boiler room.
• Take care not to store corrosive products near the boiler, such as
paints, solvents, chlorine, salt, soap and other cleaning products.
Access
The boiler room must be large enough to allow good access
to the boiler. The following minimum distances (mm) are required
around the boiler:
- front
500
- behind
150
- sides
100
- above
700
Ventilation
The boiler room must be fitted with top and bottom vents as shown
in illustration "L".
The table below is an example compliant with the Belgian
standard.
Ventilation
Min. fresh air requirement
Top vent (A)
Bottom vent (B)
Draught regulator (C)
Note:
(B) and (C) only for B23 type connections
For other countries, refer to their regulations.
Base
The base on which the boiler rests must be made of noncombustible
materials.

CHIMNEY CONNECTIONS

IMPORTANT
Boilers must be installed by a qualified heating
engineer, in accordance with the prevailing local
standards and regulations.
The chimney diameter must not be less than the
diameter of the boiler connection.
EN
6
FV/35
FV/50
m
3
/h
63
90
dm
2
1.5
1.5
dm
2
1.5
2
Ø
80
100
Chimney connection type: B23
The boiler is connected to the chimney by a metal pipe
rising at an angle from the boiler to the chimney.
Un raccord de cheminée est nécessaire.
A. Ventilation haute
B. Ventilation basse
C. Régulateur de tirage
D. Regard de visite
E. Hauteur de la cheminée tubée
F. Diamètre de la cheminée
Chimney
E = 5 m Ø min. F
mm
E = 10 m Ø min. F
mm
E = 15 m Ø min. F
mm
Note:
Since the regulations vary from one country to
another, the table above is given for information only.
Due to the high efficiency of our boilers, the flue gases
are released at high temperature.
Therefore there is a risk of condensation in these flue
gases, which could damage some chimneys.
To avoid this risk, it is strongly recommended to line
the chimney.
Contact your installer for more information.
Chimney connection type: C...
(see illustrations M and N)
• C 13 : concentric horizontal connection
• C 33 : concentric vertical connection
• C 43 : Concentric chimney connection
Maximum length for concentric type : 6 metres
Note:
A pipe bend of 90° = an equivalent length of one metre
There should be a drain outlet close to the boiler to
prevent chimney condensates entering the boiler.
To prevent condensation water running out of the
terminal, all horizontal pipes should slope down to the
boiler.
(See illustration L)
FV/35
FV/50
213
236
179
199
162
179