Top Vent Configuration With Horizontal Termination - Travis Industries 564 SS GSR2 Installation Manual

Vented gas fireplace heater
Hide thumbs Also See for 564 SS GSR2:
Table of Contents

Advertisement

Top Vent Configuration with Horizontal Termination

The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and
diffuser positions.
Up to four elbows (45° or 90°) may be used.
May use 8" (203mm) or 6-5/8" (168mm) diameter vent (see page for 21 details).
Only one horizontal elbow may be used.
21' max (6.4m)
20 feet (6m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
This is considered a horizontal
elbow (it does not matter
whether it turns right or left).
It may be a 90° or 45° elbow.
© Travis Industries
Installation
(for qualified installers only)
Exhaust Restrictor # 4
Intake Restrictor # 2
Diffuser Position # 2
H2
H1
Exhaust Restrictor # 5
Intake Restrictor # 2
Diffuser Position # 2
Exhaust Restrictor # 2
Intake Restrictor # 1 (stock)
Diffuser Position # 1 (stock)
Horizontal length is calculated by adding
both lengths of horizontal run
(Horizontal Length = H1 + H2).
This is considered a
vertical elbow
4141013
29
21' max (6.4m)
20 feet (6m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
100-01393