Start-up
Final checks before starting the boiler
 Read this manual to familiarize yourself with boiler
control module operation. Reference page 55 for proper
steps to start boiler.
 Verify the boiler and system are full of water and all
system components are correctly set for operation.
 Verify the preparation procedures of Section 10, pages 52
and 53 have been completed.
 Verify electrical connections are correct and securely
attached.
 Inspect vent piping and air piping for signs of deterioration
from corrosion, physical damage or sagging. Verify air
piping and vent piping are intact and correctly installed
per this manual.

Start the boiler

1. Read and follow the Operating instructions in FIG. 10-2,
page 55.
If boiler does not start correctly
1. Check for loose connections, blown fuse or service switch
off?
2. Is boiler water temperature above 200°F?
3. Is thermostat set below room temperature?
4. Is gas turned on at meter or boiler?
5. Is incoming gas pressure less than 4 inches w.c.?
If none of the above corrects the problem, refer to the
Troubleshooting Section.
Check system and boiler
 Check water piping
1. Check system piping for leaks. If found, shut down
the boiler and repair immediately. (See WARNINGS
on pages 52 and 53 (startup) regarding failure to repair
leaks.)
2. Vent any remaining air from the system using manual
vents. Air in the system will interfere with circulation
and cause heat distribution problems and noise.
54
Installation & Service Manual
 Check vent piping and air piping
1. Check for gastight seal at every connection, seam of air
piping, and vent piping.
Venting system must be sealed gastight
WARNING
to prevent flue gas spillage and carbon
monoxide emissions, which will result in
severe personal injury or death.
 Check gas piping
1. Check around the boiler for gas odor following the
procedure on page 42 of this manual (connecting gas supply
piping).
If you discover evidence of any gas leak,
WARNING
shut down the boiler at once.
leak source with a bubble test and repair
immediately. Do not start the boiler again
until corrected. Failure to comply could
result in severe personal injury, death, or
substantial property damage.
 Propane boilers – verify conversion
1. Verify propane conversion has been completed per the
Propane Conversion instructions.
DO NOT adjust gas valve outlet pressure.
WARNING
The gas valve is factory-set for the correct
outlet pressure.
for natural gas and propane, requiring
no field adjustment. Attempting to alter
the gas valve outlet pressure could result
in damage to the valve, causing potential
severe personal injury, death, or substantial
property damage.
Cadet heating boilers are typically shipped
WARNING
ready to fire on natural gas. Check boiler
rating plate to determine which fuel the
boiler is set for. If set to natural gas, it may
be converted to LP by installing an orifice
(see page 12). In order to operate on LP
gas, an orifice MUST BE installed. Failure
to comply could result in severe personal
injury, death, or substantial property
damage.
Check flame and combustion
1. Turn the main power off to the boiler.
2. Remove the flue temperature sensor from the heat
exchanger. Note: Combustion measurements will be made
at this point.
Find the
This setting is suitable