Remove Boiler From Wood Pallet; Mounting The Boiler - Cadet 40-120 Installation And Service Manual

Table of Contents

Advertisement

2
Prepare boiler
3. Remove the two (2) lag bolts securing the wall bracket to
the wood pallet. Be certain not to lose the wall bracket as
it will be needed for securing the boiler to the wall (FIG.
2-4).
Do not drop the boiler. Damage to the
NOTICE
boiler can result.
Figure 2-3 Acceptable Lifting Locations
Figure 2-4 Boiler Mounted on Shipping Pallet

Mounting the boiler

See page 9 of this manual for boiler mounting location
instructions.
The Cadet heating boiler is not intended
NOTICE
for floor installation.
Mounting to a wood studded wall:
1.
The wall mount bracket is designed for a stud spacing of
16 inches from center (FIG. 2-5). For other stud spacing
a solid mounting surface must be provided by the
installer.
WARNING Do not mount the boiler to a hollow wall.
Be sure to mount the boiler to the studs
only.
(continued)
IMG00268
REMOVE SHIPPING
[WALL] BRACKET
DO NOT DISCARD-
WILL BE NEEDED TO
SECURE THE BOILER
TO THE WALL
IMG00212
Installation & Service Manual
2.
Mount the wall bracket using the 2 1/4" lag bolts
provided. Make sure the top edge of the bracket is away
from the wall. Ensure the bracket is level when mounted.
Extreme care is needed to ensure the bolts are secured in
the center of the studs.
3.
Hang the boiler on the bracket and secure the bottom of
the boiler with two (2) additional lag bolts provided.
WARNING The boiler is too heavy for a single person
to lift.
needed for mounting the boiler onto the
bracket.
Mounting to a concrete wall:
1.
Mount the wall bracket using the two (2) wedge anchor
bolts provided with the bracket (FIG. 2-5). To mount the
wedge anchor bolts, drill a 1/4" diameter hole 1 1/8" deep
and insert anchor. Hang the bracket from the anchor and
secure with the two nuts provided. Make sure the top edge
of the bracket is away from the wall. Ensure bracket is level
when mounted.
Note: If wall thickness does not allow a 1 1/8" deep hole,
field supplied hardware suitable for the application should be
provided.
2.
Hang the boiler on the bracket and secure the bottom of the
boiler with two (2) remaining anchors, following the
instructions above.
Mounting to a metal studded wall:
1.
The wall mount bracket is designed for a stud spacing of 16
inches from center (FIG. 2-5). For other stud spacing a
solid mounting surface must be provided by the installer.
Do not mount the boiler to a hollow wall. Be
WARNING
sure to mount the boiler to the studs only.
2.
Mount the wall bracket using two (2) field supplied toggle
bolts capable of supporting 100 pounds each. Ensure the
top edge of the bracket is away from the wall. Ensure the
bracket is level when mounted. Extreme care is needed to
ensure the bolts are secured in the center of the studs.
3.
Hang the boiler on the bracket and secure the bottom of the
boiler with two (2) field supplied toggle bolts.
Figure 2-5 Mounting the Boiler
FASTENERS
APPROPRIATE
FOR WALL TYPE
QTY: 4
A minimum of two people is
WALL:
WOOD OR METAL STUDS
ON 16" CENTERS -OR-
MASONRY / POURED CONCRETE
MOUNTING BRACKET
(FACTORY SUPPLIED)
IMG00213
13