Installation Of Outdoor Unit - Toshiba RAV-SM1104ATP-E Installation Manual

Air conditioner (split type)
Hide thumbs Also See for RAV-SM1104ATP-E:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Obstacle in front
Above unit is free
1. Single unit installation
2. Serial installation of two or more units
Obstacle also at the above unit
1,000 or
more
63-EN
1115250101_EN.indd 32
1115250101_EN.indd 32
Obstacles in both front and rear of unit
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of
the unit, should be lower than the height of the outdoor
unit.
Standard installation
1. Single unit installation
2. Serial installation of two or more units
300 or
300 or
more
more
Serial installation in front and rear
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of
the unit, should be lower than the height of the outdoor
unit.
Standard installation
1,000 or
300 or
1,500 or
2,000 or
200 or
more
more
more
more
more

Installation of outdoor unit

Before installation, check the strength and
horizontalness of the base so that abnormal sounds
do not emanate.
According to the following base diagram, fix the base
firmly with the anchor bolts.
(Anchor bolt, nut: M10 x 4 pairs)
Drain hole
525
150
600
150
Drain hole
Drain nipple
mounting hole
As shown in the figure below, install the foundation
and vibration-proof rubber pads to directly support
the bottom surface of the fixing leg that is in contact
with and underneath the bottom plate of the outdoor
unit.
* When installing the foundation for an outdoor unit
with downward piping, consider the piping work.
Correct
Absorb vibration
with vibration-
proof rubber
pads
Fixing leg
Foundation
Correct
Bottom plate of
outdoor unit
Foundation
Support the bottom surface of the fixing
leg that is in contact with and underneath
the bottom plate of the outdoor unit.
In correct
Do not support
If only the end of
the outdoor unit
the fixing leg is
supported, it may
only with the
fixing leg.
deform.
Foundation
– 32 –
Set the out margin of the anchor bolt to 15 mm or less.
15 or less
When water is to be drained through the drain hose,
attach the following drain nipple and waterproof
rubber cap, and use the drain hose (Inner dia.:
16 mm) sold on the market. Also seal knockout hole
and the screws securely with silicone material, etc.,
to prevent water from leaking.
Some conditions may cause dewing or dripping of
water.
When collectively draining discharged water
completely, use a drain pan.
Waterproof rubber cap
Drain nipple
(5 pcs.)
Drain nipple
Knockout hole
Waterproof rubber cap
For reference
If a heating operation is to be continuously performed
for a long time under the condition that the outdoor
temperature is 0 °C or lower, draining defrosted water
may be difficult due to the bottom plate freezing,
resulting in trouble with the cabinet or fan.
It is recommended to procure an anti-freeze heater
locally in order to safely install the air conditioner.
For details, contact the dealer.
8/24/13 9:21 AM
8/24/13 9:21 AM
EN
ID
64-EN