Comp. Down Due To A Discharge Temperature Sensor Of A Compressor (Error Code : E416) - Samsung AM036FXMDCH Service Manual

System air conditioner
Hide thumbs Also See for AM036FXMDCH:
Table of Contents

Advertisement

3-9 Comp. down due to a discharge temperature sensor of a compressor
(Error Code : E416)
1. How to check
Is the discharge sensor
resistance of the compressor
normal? (refer to E251)
Are service valves open?
of S-net and Manifold gauge
Does indoor/outdoor EEV
clogged place in the piping
Samsung Electronics
Yes
Test operation
Do the values
correspond?
Yes
operate well?
No
Is there any
(ex. filter)?
Check the amount of
refrigerant
No
Replace discharge temperature sensor
Connect S-net and Manifold gauge
(Mandatory)
No
Open the service valve
No
Replace a high pressure sensor
Yes
Check the relevant EEV
Check the piping
Troubleshooting
29

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Am048fxmdchAm053fxmdch

Table of Contents