Comp. Down Due To A Discharge Temperature Sensor Of A Compressor (Error Code : E416) - Samsung AM040FXMDEH Service Manual

System air conditioner
Hide thumbs Also See for AM040FXMDEH:
Table of Contents

Advertisement

Troubleshooting
3-9 Comp. down due to a discharge temperature sensor of a compressor
(Error Code : E416)
1. How to check
discharge sensor resistance
of the compressor normal?
Are service valves open?
of S-net and Manifold gauge
Does indoor/outdoor EEV
clogged place in the piping
Check the amount of
40
Is the
(refer to E251)
Yes
Test operation
Do the values
correspond?
Yes
operate well?
No
Is there any
(ex. filter)?
refrigerant
No
Replace discharge temperature sensor
Connect S-net and Manifold gauge
(Mandatory)
No
Open the service valve
No
Replace a high pressure sensor
Yes
Check the relevant EEV
Check the piping