Press and release T. Wait for the test to complete.
4.
The primary (upper) display shows the line
impedance.
The secondary (lower) display shows the
Prospective Short Circuit Current (PSC). PSC is
the current that would flow in case of a Line to
Neutral short. It is calculated by dividing mains
voltage by line impedance.
Use the connection shown in Figure 14 when measuring in
a 3-phase system.
N (L3/Blue)
Figure 14. Measuring in a 3-Phase System
Electrical Installation Tester
Making Measurements
L1
L2
L3
L (L1/Red)
apx025f.eps