WELDER OPERATION

WELDER OUTPUT
• Maximum Open Circuit Voltage at 3700 RPM is 80
Volts RMS.
• Duty Cycle is the percentage of time the load is
being applied in a 10 minute period. For example, a
60% duty cycle represents 6 minutes of load and 4
minutes of no load in a 10 minute period. Duty
Cycle for the RANGER® 3 PHASE is 100%.
RANGER® 3 PhASE
Constant Current
210 Amps DC @ 25 Volts
Constant Voltage
200 Amps DC @ 20 Volts

AUXILIARY POWER

CAUTION
Do not connect any plugs that connect to the
power receptacles in parallel.
------------------------------------------------------------------------
Start the engine and set the "IDLER" control switch
to the "High Idle" mode. Set the "CONTROL" to 10.
Voltage is now correct at the receptacles for auxiliary
power. This must be done before a tripped GFCI
receptacle can be reset properly. See the MAINTE-
NANCE section for more detailed information on
testing and resetting the GFCI receptacle.
The RANGER 3 PHASE can provide both three phase
and single phase power, up to 11,500 watts of 480
volts AC, three phase 60Hz power for peak use, and
up to 10,500 watts of 480 volts AC, three phase 60Hz
power for continuous use, up to 10,500 watts of
120/240 volts AC, single phase 60Hz power for peak
use, and up to 9,500 watts of 120/240 volt AC, single
phase 60Hz power for continuous use. The front of
the machine includes four receptacles for connecting
the AC power plugs; one 20 amp 480 volt 3 phase
NEMA receptacle, one 50 amp 120/240 volt NEMA
14-50R receptacle and two 20 amp 120 volt NEMA 5-
20R receptacles. Output voltage is within +/-10% at all
loads up to rated capacity. Do not use 3 phase
power and single phase power simultaneously. All
auxiliary power is protected by cuircuit breakers.
RANGER 3 PhASE Extension Cord Length Recommendations
(Use the shortest length extension cord possible sized per the following table.)
Current
Load
Voltage
(Amps)
Volts
(Watts)
15
120
1800
20
120
2400
15
240
3600
20
240
4800
40
240
9500
INSTALLATION
Maximum Allowable Cord Length in ft. (m) for Conductor Size
14 AWG
12 AWG
(9)
(12)
30
40
30
(9)
(18)
(23)
60
75
60
(18)
Conductor size is based on maximum 2.0% voltage drop.
RANGER® 3 PhASE
120/240 VOLT DUAL VOLTAGE RECEPTACLE
The 120/240 volt receptacle can supply up to 40
amps of 240 volt power to a two wire circuit, up to 40
amps of 120 volts power from each side of a three
wire circuit (up to 80 amps total). Do not connect the
120 volt circuits in parallel. Current sensing for the
automatic idle feature is only in one leg of the three
wire circuit as shown in the following column.
G N D
* C u r r e n t S e n s i n g f o r A u t o m a t i c I d l e .
( R e c e p t a c l e v i e w e d f r o m f r o n t o f M a c h i n e )
2 4 0 V
1 2 0 V *
1 2 0 V
*Current Sensing for Automatic Idle.
(Receptacle viewed from front of Machine)
120 V GFCI DUPLEX RECEPTACLES
A GFCI (Ground Fault Circuit Interrupter) electrical
receptacle is a device to protect against electric shock
should a piece of defective equipment connected to it
develop a ground fault. If this situation should occur,
the GFCI will trip, removing voltage from the output of
the receptacle. If a GFCI receptacle is tripped see the
MAINTENANCE section for detailed information on
testing and resetting it. A GFCI receptacle should be
properly tested at least once every month.
The 120V auxiliary power receptacles should only be
used with three wire grounded type plugs or approved
double insulated tools with two wire plugs.
The current rating of any plug used with the system
must be at least equal to the current load through the
associated receptacle.
480 Volt 3 Phase Receptacle with Ground
The 480 volt receptacle can supply 12.6 amps of 3
phase power, or up to 15 amps of single phase
power. A NEMA plug L16-20P is required to use this
receptacle. The ground (GND) connection is connect-
ed to the machine frame, it is NOT the neutral of the
three phase connection, and should under no circum-
stances be connected to the neutral of any 3 phase
load. Do not connect 480V 3 phase to single phase

premises wiring.

10 AWG
8 AWG
(23)
125
(38)
75
(15)
(27)
50
88
(69)
(46)
225
150
(30)
(53)
100
175
(27)
(15)
90
50
A-6
GND
120 V
240 V
120 V*
6 AWG
4 AWG
175
(53)
300
(91)
138
(42)
(69)
225
350
(183)
(107)
600
275
(84)
(137)
450
150
(69)
(46)
225