Ambient Sensor The ambient sensor (shown in figure
21) considers outdoor temperatures below −35°F (−37°C)
or above 120°F (48°C) as a fault. If the ambient sensor is
detected as being open, shorted or out of the temperature
range of the sensor, the board will not perform demand de-
frost operation. The board will revert to time/temperature
defrost operation and will display the appropriate fault
code. Heating and cooling operation will be allowed in this
fault condition.
NOTE − Within a single room thermostat demand, if
5−strikes occur, the board will lockout the unit. Defrost
board 24 volt power R" must be cycled OFF" or the
TEST" pins on board must be shorted between 1 to 2 sec-
onds to reset the board.
AMBIENT
SENSOR
Figure 21. Sensor Locations
Defrost Temperature Termination Shunt (Jumper)
Pins The defrost board selections are: 50, 70, 90, and
100°F (10, 21, 32 and 38°C). The shunt termination pin is
factory set at 50°F (10°C). If the temperature shunt is not
installed, the default termination temperature is 90°F
(32°C).
DELAY MODE
The defrost board has a field−selectable function to reduce
occasional sounds that may occur while the unit is cycling
in and out of the defrost mode. When a jumper is installed
on the DELAY pins, the compressor will be cycled off for 30
seconds going in and out of the defrost mode. Units are
shipped with jumper installed on DELAY pins.
NOTE − The 30 second off cycle is NOT functional when
jumpering the TEST pins.