4.HYDRO UNIT
Average heating capacity and power input
Capacity (kW)
-20
-15
-7
-2
2
TO
(°C)
7
10
12
15
20
Power input (kW)
-20
-15
-7
-2
2
TO
(°C)
7
10
12
15
20
COP
-20
-15
-7
-2
2
TO
(°C)
7
10
12
15
20
* Heating capacity and power input are include defrost cycle data.
* Heating capacity and power input are shown at maximum operating frequency
* Power input does not include water pump power.
* Heating capacity and power input are measured in accordance with EN14511.
TO
:
Outdoor temperature (DB°C) RH85%
LWT
:
Leaving water temperature (°C)
30
35
6.43
6.18
8.26
7.94
9.75
9.37
11.37
10.93
12.03
11.56
17.77
17.08
18.66
17.93
19.92
18.96
21.53
20.09
23.89
21.87
30
35
3.24
3.50
3.41
3.69
3.80
4.10
3.74
4.04
3.69
3.98
3.65
3.94
3.65
3.94
3.66
3.95
3.69
3.98
3.48
3.75
30
35
1.98
1.77
2.42
2.15
2.57
2.29
3.04
2.71
3.26
2.90
4.87
4.34
5.11
4.55
5.44
4.80
5.83
5.05
6.86
5.83
36
LWT (°C)
40
45
5.94
—
—
7.64
—
—
9.01
8.24
—
10.52
9.61
11.12
10.17
16.43
15.02
17.25
15.77
18.24
16.67
19.33
17.67
21.04
19.23
LWT (°C)
40
45
3.76
—
—
3.96
—
—
4.40
4.42
—
4.34
4.36
4.27
4.29
4.23
4.25
4.23
4.25
4.24
4.26
4.28
4.30
4.03
4.05
LWT (°C)
40
45
1.58
—
—
1.93
—
—
2.05
1.86
—
2.42
2.20
2.60
2.37
3.88
3.53
4.08
3.71
4.30
3.91
4.52
4.11
5.22
4.75
Engineering Data book
50
55
—
—
—
8.66
—
9.16
8.62
13.53
12.13
14.21
12.74
15.02
13.47
15.91
14.27
17.32
15.53
50
55
—
—
—
4.38
—
4.31
4.34
4.27
4.30
4.27
4.30
4.28
4.31
4.32
4.35
4.07
4.10
50
55
—
—
—
1.98
—
2.13
1.99
3.17
2.82
3.33
2.96
3.51
3.13
3.68
3.28
4.26
3.79
4