3.SYSTEM SPECIFICATION
Outdoor unit
Hydro unit
Capacity
Rated heating
Power input
condition
TO (DB/WB)=7/6°C
COP
LWT=35°C dT=5deg
Rated water flow
Capacity
Rated heating
Power input
condition
TO (DB/WB)=7/6°C
COP
LWT=45°C dT=5deg
Rated water flow
Capacity
Rated cooling
Power input
condition
TO=35°C
EER
LWT=7°C dT=5deg
Rated water flow rate
Capacity
Rated cooling
Power input
condition
TO=35°C
EER
LWT=18°C dT=5deg
Rated water flow
Power supply
Maximum current
* Rated condition capacity and power input are the data at rated compressor operating frequency.
* Power input does not include water pump power.
* Capacity and power input are measured in accordance with EN14511.
TO
:
Outdoor temperature (°C)
LWT
:
Leaving water temperature (°C)
dT
:
Delta temperature (deg)
Leaving water temperature - return water temperature (Heating)
Return water temperature - leaving water temperature (Cooling)
HWS-802H-E
HWS-802XWH**-E
kW
8.0
kW
1.96
W/W
4.08
/min
22.9
kW
8.0
kW
2.40
W/W
3.33
/min
22.9
kW
6.0
kW
2.13
W/W
2.82
/min
17.2
kW
6.0
kW
1.42
W/W
4.23
/min
17.2
A
20.8
10
Engineering Data book
HWS-1102H-E
HWS-1402H-E
HWS-1402XWH**-E
11.2
2.4
4.66
32.1
11.2
2.95
3.80
32.1
10.0
3.52
2.84
28.7
10
2.35
4.26
28.7
1~ 230V 50Hz
22.8
14.0
3.15
4.45
40.1
14.0
3.95
3.54
40.1
11.0
4.08
2.69
31.5
11
2.65
4.15
31.5
22.8
3