12.1.5
Automatic Operation
•
This mode can be set using remote control and the operation is decided by remote control setting temperature,
remote control operation mode and indoor intake air temperature.
•
During operation mode judgment, indoor fan motor (with speed of Lo-) is running for 30 seconds to detect the
indoor intake air temperature.
•
Every 10 minutes, the indoor temperature is judged.
•
For the 1st judgment
If indoor intake temperature - remote control setting temperature ≥ 2°C, COOL mode is decided.
o
If -2°C ≤ indoor intake temperature - remote control setting temperature < 2°C, DRY mode is decided.
o
If indoor intake temperature - remote control setting temperature < -2°C, HEAT mode is decided.
o
•
For the 2nd judgment onwards
If indoor intake temperature - remote control setting temperature ≥ 3°C, if previous operate in DRY mode,
o
then continue in DRY mode. otherwise COOL mode is decided.
If -2°C ≤ indoor intake temperature - remote control setting temperature < 3°C, maintain with previous mode.
o
If indoor intake temperature - remote control setting temperature < -2°C, HEAT mode is decided.
o
12.1.6
Fan Operation
•
Fan Operation is used to circulate air in a room.
•
During operation, indoor fan run continuously but outdoor fan and compressor stop.
•
Temperature setting is not applicable.
12.2 Indoor Fan Motor Operation
A. Basic Rotation Speed (rpm)
i. Manual Fan Speed
[Cooling, Dry, Fan]
•
Fan motor's number of rotation is determined according to remote control setting.
Remote control
[Heating]
•
Fan motor's number of rotation is determined according to remote control setting.
Remote control
○
Tab
Hi
○
Tab
SHi
○
○
Me+
Me
○
○
Me+
Me
34
○
○
Me-
Lo
○
○
Me-
Lo