Dimensions and ratings
Boiler dimensional and physical data (see Figure 103, page 98)
Figure 104
Supply
Boiler
model
(inches NPT
male)
GWC-070
1
GWC-105
1
GWC-140
1
GWC-175
1
Note 1: Gas piping from meter to boiler to be sized per local utility requirements.
Boiler ratings
Figure 105
Boiler
CSA
model
Input
Heating
capacity
(Note 1)
MBH
GWC-070
70
GWC-105
105
GWC-140
140
175
GWC-175
Notes:
1. Based on standard test procedures prescribed by the United States Department of Energy. Ratings also
referred to as CSA Output. NOTE that only DOE Heating Capacity and AFUE are certified by AHRI. AFUE is
also know as Annual Fuel Utilization Efficiency or Seasonal Efficiency.
2. Net I=B=R ratings are based on net installed radiation of sufficient quantity for the requirements of the building
and nothing need be added for normal piping and pickup. Ratings are based on a piping and pickup allowance
of 1.15 and are determined under the provisions governing forced draft boiler-burner units. An additional
allowance should be made for unusual piping and pickup loads.
3. All of the boilers will automatically de-rate as vent length increases, due to the pressure loss through the vent.
For vent/air pipe lengths less than the maximum, the derate equals the value above times vent length ÷ 100.
4. Boilers are tested for 50 PSIG working pressure.
5. GWC boilers are not available for millivolt systems.
Part number 550-142-056/0411
— Boiler Manual
Return
Length
L
(inches NPT
(inches)
female)
1
30¾
1
30¾
1
37¾
1
37¾
DOE
Net I=B=R
AFUE
water
(Note 1)
rating
(Note 2)
MBH
MBH
%
65
56
91.9
97
84
91.2
130
113
91.4
161
140
91.0
(continued)
Gas
Electrical
connection
service
size
required
(Note 1)
(includes
the internal
circulators)
(inches NPT
(amperes)
female)
½
½
½
½
Vent/
Boiler
combustion
water
(Values shown are at maximum vent/air pipe length)
air diameter
content
Direct Exhaust Venting
Inches
Gallons
Natural gas
3" PVC
3.8
up to 0.7%
3" PVC
4.7
up to 1.0%
3" PVC
6.0
up to 4.0%
3" PVC
6.9
up to 4.0%
Boiler
water
content
(gallons)
15
3.8
15
4.7
15
6.0
15
6.9
DOE
% Input derate vs vent length
(Note 3)
Direct Vent Venting
Propane
Natural gas
up to 1.4%
up to 1.5%
up to 2.2%
up to 4.0%
up to 4.0%
up to 7.0%
up to 4.5%
up to 7.0%
Approx.
shipping
weight
(pounds)
313
353
423
464
Propane
up to 2.8%
up to 5.4%
up to 8.0%
up to 10.0%
99