Mitsubishi Heavy Industries FDTC40ZIXVD Data Book page 269

Standard inverter packaged air-conditioners
Table of Contents

Advertisement

Model
Item
Power source
Operation data
Nominal capacity
kW
Sound Pressure Level
dB(A)
Exterior dimensions
mm
Height x Width x Depth
Exterior appearance
(Munsell color)
Net weight
kg
Refrigerant equipment
Compressor type & Q'ty
Starting method
Refrigerant oil
Heat exchanger
Refrigerant control
Air handling equipment
Fan type & Q'ty
Motor <Starting method>
Air flow (Standard)
CMM
Shock & vibration absorber
Electric heater
Safety equipment
Installation data
mm
Refrigerant piping size
Connecting method
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Refrigerant Quantity
Drain
Insulation for piping
Standard Accessories
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
Cooling
Heating
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
Cooling
25.0 [ 10.0 (Min.)~28.0 (Max.)]
W
W
Max.30m (Outdoor unit is higher)
Max.15m (Outdoor unit is lower)
R410A 7.2kg (Pre-charged up to the piping length of 30m) Outdoor unit
Outdoor air temperature
DB
WB
DB
27˚C
19˚C
35˚C
20˚C
7˚C
FDC250VS
380-415V 3N~50Hz / 380V 3N~60Hz
Cooling : 57 Heating : 58
1,505 × 970 × 370
Stucco White
(4.2Y7.5/1.1) near equivalent
140
GTC5150ND70K × 1
Direct line start
1.45 M-MA32R
Straight fin & inner grooved tubing
Electronic expansion valve
Propeller fan × 2
86 × 2 < Direct line start >
Cooling : 150, Heating : 145
Rubber sleeve (for Compressor )
33 (Crank case heater)
Internal thermostat for fan motor
Abnormal discharge temperature protection.
Liquid line :φ12.7 (1/2")
Gas line
:φ22.22 (7/8")
Liquid : Flare / Gas : Brazing
Max.70m
Holes size φ20 × 3pcs
Necessary (both Liquid & Gas lines)
Connecting pipe, Edging
WB
24˚C
6˚C
-
-
268
'10 • PAC-DB-142
Adapted to RoHS directive
Heating
28.0 [ 9.5 (Min.)~31.5 (Max.)]
1.See page 154
PJF000Z188