Mitsubishi Heavy Industries FDTC40ZIXVD Data Book page 149

Standard inverter packaged air-conditioners
Table of Contents

Advertisement

Models 200, 250
Indoor unit
Indoor unit
Refrigerant line (one way) pipe size
Model
Gas line
200
In case of ø22.22 : 35m
In case of ø25.4 or ø28.58 : 70m
250
Gas branch pipe
ø
(
15.88)
Outdoor unit
Gas line
Service valve
(Flare connecting)
Flare connecting
Thermistor
(Heat exchanger)
(ThI-R3)
Thermistor
(Return air)
(ThI-A)
Heat exchanger
Thermistor
(Heat exchanger)
(ThI-R2)
Thermistor
(Heat exchanger)
(ThI-R1)
Flare connecting
Liquid line
Service valve
(Flare connecting)
Liquid
branch pipe
ø
(
9.52)
Liquid line
In case of ø9.52 : 40m
In case of ø12.7 : 70m
In case of ø12.7 : 70m
-
-
148
Cooling cycle
Check joint
4way valve
Muffler
High pressure
switch
63H
Check
valve
Oil
separator
Strainer
Thermistor
(ThO-D)
Capillaly
(Discharge)
tube
Compressor
(Suction)
Thermistor
(ThO-H)
Check joint
Strainer
Strainer
Electronic
expansion
valve
(cooling)
Receiver
(EEVC)
Receiver
'10 • PAC-DB-142
Heating cycle
Thermistor
(ThO-A)
Check joint
Lower pressure
sensor
(LPT)
Heat exchanger
Thermistor
(ThO-S)
Thermistor
Thermistor
(ThO-R2)
(ThO-R1)
Sub-cooling
coil
Strainer
Strainer
Electronic
expansion
valve
(heating)(EEVH)