Mitsubishi Heavy Industries FDTC40ZIXVD Data Book page 152

Standard inverter packaged air-conditioners
Table of Contents

Advertisement

Preset point of the protective devices
Parts name
Thermistor
(for protection over-
loading in heating)
Thermistor
(for frost prevention)
Thermistor
(for protection high
pressure in cooling.)
Thermistor
(for detecting dis-
charge pipe temp.)
High pressure switch
(for protection)
Low pressure sensor
(for protection)
Equipped
Mark
unit
Th
-R
I
Indoor unit
Tho-R
Outdoor unit
(TH1)
Tho-D
Outdoor unit
(TH3)
63H1
Outdoor unit
LPT
Outdoor unit
40, 50, 60 model
71, 100, 125, 140 model
OFF 53˚C
ON 63˚C
OFF 115˚C
ON 95˚C
-
-
151
'10 • PAC-DB-142
200, 250 model
OFF 63˚C
ON 56˚C
OFF 1.0˚C
ON 10˚C
OFF 51˚C
ON 65˚C
OFF 115˚C
OFF 135˚C
ON 85˚C
ON 90˚C
OFF 4.15MPa
ON 3.15MPa
OFF 0.227MPa
ON 0.079MPa