Lennox FCM 85 Installation, Operating And Maintenance page 53

Flexy & flexy wshp series
Table of Contents

Advertisement

VENTILATION : AIRFLOW BALANCING
nd
2
method when adjusting the pulley :
-Close the pulley fully and count the number of turns
from fully closed position. Using table_1 determine the
motor pulley actual diameter.
-Record the fix fan pulley diameter.(DF)
-Determine the fan speed using the following formulae:
=
rpm
rpm
FAN
Where: rpm
:from the motor plate or table_2
MOTOR
D
: from table_1
M
D
: from machine
F
Once the pulleys are adjusted and the belt checked and
tensioned, start the fan motor and record the Amps and
Voltage between the phases:
Using the measured data and table_2
-Theoretical mechanical power at the fan shaft:
η
P
= P
x
meca fan
meca Motor
Transmission
η
P
= P
x
meca fan
elec
meca motor
= V x I x √3 x cosϕ x η
P
meca fan
This formula can be approximated in this way
P
= V x I x 1.73 x 0.85 x 0.76 x 0.9
meca fan
With the fan "rpm" and the mechanical power at the fan
shaft an operating point and the supplied airflow can be
estimated using the fan curves.
Table_3 Accessories pressure drops
Economiser
12000
12
85
15000
19
23000
45
14000
17
100
18500
29
23000
45
15000
19
120
20500
36
23000
45
18000
6
150
26000
12
35000
22
21000
8
170
30000
16
35000
22
24000
12
200
35000
26
43000
39
27000
15
39000
32
230
43000
39
FLEXYII_WSHP-IOM-0909-E
×
D
/D
MOTOR
M
F
η
x
Transmission
x η
meca motor
Transmission
UV
Hot
G4
F7
LIGH
Water
Filters
Filters
T
coil S
1
75
18
9
7
105
30
13
28
199
63
26
5
94
26
11
15
143
44
18
28
199
63
26
7
105
30
13
21
167
52
21
28
199
63
26
1
75
15
6
12
130
33
12
29
204
54
19
5
94
21
8
19
161
42
15
29
204
54
19
3
88
18
7
18
154
39
13
31
211
54
19
7
105
24
8
24
182
46
16
31
211
54
19
CHECKING AIRFLOW AND ESP
Using the fan curves on page 36 to 40, the airflow, the total
pressure available (P
pressure (Pd) can now be estimated, for a specific
operating point;
The next step consists in estimating the pressure losses
across the unit.
This can be achieved using the "dirty filter pressure sensor"
and the accessories pressure drop table: table_3
Also the pressure drop due to the duct inlet into the roof-top
unit can be taken as 20 to 30 Pa.
P
INT
Using the results from above, the external static pressure
(ESP) can then be estimated:
Table_ 2 Motor information
Motor Size
0.75 kW
1.1kW
1.5kW
2.2kW
3.0kW
4kW
5.5kW
7.5kW
9.0kW
11.0kW
Hot
Electric
Electric
Electric
Water
Heater
Heater
Heater
coil H
S
M
H
15
3
5
6
22
6
7
7
44
7
9
11
19
6
7
8
31
8
10
11
44
11
14
16
22
7
8
9
37
10
12
13
44
12
15
17
10
4
5
7
19
9
10
13
33
15
18
23
14
8
9
10
25
10
13
15
33
17
19
21
11
16
15
14
22
22
21
20
31
24
26
29
14
18
18
17
26
24
24
25
31
24
26
29
) and the corresponding dynamic
TOT
=
P
+
P
+
P
filter + coil
Inlet
ESP = P
- Pd -
P
TOT
INT
Cos ϕ
Nom. Speed
1400 rpm
0.77
1429 rpm
0.84
1428 rpm
0.82
1436 rpm
0.81
1437 rpm
0.81
1438 rpm
0.83
1447 rpm
0.85
1451 rpm
0.82
1455 rpm
0.82
1451 rpm
0.85
Heating
Multidire
Adjustable
Gaz
ctional
roofcurb
fired H
Roofcurb
14
17
22
23
27
33
53
63
73
20
23
30
34
41
51
53
63
78
23
27
35
42
50
62
53
63
78
16
30
35
33
62
72
59
112
131
21
40
49
44
82
95
59
112
131
21
53
67
44
112
133
66
169
195
26
67
84
55
139
163
66
169
195
Options
η
meca motor
0.70
0.77
0.79
0.81
0.83
0.84
0.86
0.87
0.88
0.88
Heat
Recovery
Modul
Fresh Air
164
204
313
191
252
313
204
279
313
170
245
329
198
282
329
173
252
310
195
281
310
Page 51

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents