Telephone Jack Only Audio Circuit - Fire-Lite ECC-FFT Instruction Manual

Firefighter’s telephone
Table of Contents

Advertisement

Audio Phone Circuit Installation

Telephone Jack Only Audio Circuit

The FFT can also be configured using only the Fire Fighters Phone Jack (FPJ-F). In this configura-
tion, the MMF-301 module is not required for system operation. To configure the FFT for Tele-
phone Jack only, the DIP Switch position 1 must be off (SLC Devices not Installed). See Table 2.1
on page 13.
Audio wiring for this configuration is detailed below. See Figures 2.15 and 2.16.
+ Audio
- Audio
FFT
Figure 2.15 Telephone Jack Only Audio Circuit in Class B
ECC-FFT Instruction Manual — P/N LS10031-000FL-E:B 9/4/2013
3
1
2
2
1
3
TB1
TB2
FPJ-F
Caution
For system supervision-
3
1
For terminals 2 and 3, do not
2
2
use looped wire under
1
3
terminals. Break wire run to
TB1
provide supervision of
TB2
connections.
FPJ-F
4.7K, 1/2 watt ELR
3
1
(install on last device for
2
2
Style Y [Class B]
1
telephone circuit only)
3
TB1
TB2
FPJ-F
Installation