Installing The Ecc-Fft; 1: Operating Power; 2: Dip Switch Settings On Ecc-Fft; Dip Switch - Fire-Lite ECC-FFT Instruction Manual

Firefighter’s telephone
Table of Contents

Advertisement

Installing the ECC-FFT

2.3 Installing the ECC-FFT
2.3.1 Operating Power
Connect the ECC-FFT to the appropriate DC power source. See Section 1.3 for compatible equip-
ment and Section 1.5 for power requirements.
2.3.2 DIP switch settings on ECC-FFT
Use the on-board DIP switch to assign the configuration setting to the ECC-FFT.
1.
Refer to Figure 2.3 for location of the DIP switches on the ECC-FFT board.
2.
Configure the ECC-FFT using the dip switch settings in Table 2.1. Add SLC modules to the
system through Autoprogram feature. See Section 3.3 for Autoprogram Operation.

DIP Switch

DIP Switch
ECC-FFT Instruction Manual — P/N LS10031-000FL-E:B 9/4/2013
1
SLC Devices Installed
2
Trouble Piezo Enabled
3
SLC Class A Supervision
4
Phone Circuit Class A Supervision
5
Not Used
6
Not Used
Table 2.1 ECC-FFT DIP Switch Configurations
Figure 2.3 DIP Switch
ON
SLC Devices not Installed
Trouble Piezo Disabled
SLC Class B Supervision
Phone Circuit Class B Supervision
Leave in OFF position
Leave in OFF position
Installation
OFF
13

Advertisement

Table of Contents
loading

Table of Contents