Fpj-F Installation - Fire-Lite ECC-FFT Instruction Manual

Firefighter’s telephone
Table of Contents

Advertisement

Installation

2.6 FPJ-F Installation

The FPJ-F Firefighter Phone Jack mounts to a single-gang electrical box (4 x 2⅛ x 2½) or, when
the addressable mini-monitor module is installed with it, a deep single-gang electrical box (4" x
2⅛" x 3¼").
Connect the telephone audio loop between the FPJ-F and FFT as detailed below. All circuits are
power-limited and supervised.
16
Figure 2.6 FPJ-F (Phone Jack) and FHS-F (Handset)
Class A wiring
contact ELR connected
Audio
+
Audio
-
TB2
FFT
Figure 2.7 FFT to FPJ-F Connection
ECC-FFT Instruction Manual — P/N LS10031-000FL-E:B 9/4/2013
ADDRESS
14 15
0
0 1
1
2
13
12
3
LOOP
11
4
10
5
6
6
9
9
8
7
8
7
TENS
ONES
+
-
3
1
2
2
1
3
TB1
4.7K, ½ watt ELR
(install on last device
for Style Y [Class B]
telephone circuit only)
FPJ-F
FPJ-F Installation
2
3
4
5
To FFT-SLC
terminal TB4
connectors or other
MMF-301s