LG AS-W2463RH2 Manuals page 70

Room air conditioner
Table of Contents

Advertisement

Troubleshooting Guide
8) Troubleshooting CH61, CH62
Display
Title
code
Condenser
61
pipe sensor
temp. high
Heat sink sensor
62
temp. high
Toff °C
T2 °C
T1 °C
COMP Frequency
Normal
(Hz)
Check Point
• CH 61
1. Check the install condition for over load.
(Refrigerant, Pipe length, Blocked, ...)
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Cause of error
• Condenser pipe sensor
detected high
temp.(65°C)
• Heat sink sensor
detected high
temp.(85°C)
Heat Sink temp.
Normal
OFF
- 70 -
Check point & Normal condition
• Check the load condition.
• Check the sensor of Condenser pipe sensor.
• Check the fan is locked.
• Check the sensor of heat sink.
Normal
• CH 62
1. Check the fan is locked.
2. Check the Outdoor temp. is very high.
LGE Internal Use Only