SYSTEM CONNECTIONS
Compare this illustration with your generator to familiarize yourself with the location of these important connections:
Wiring for the 2 Pole Plug:
240 Volt Utility — Use to hook up the 240V utility leads
from the transfer switch to the generator.
Wiring for the 10 Pole Plug:
Fault Contacts — Use NO, COM and NC to hook up a
siren, light, etc. to alert you in case of a fault. Contacts
reverse state upon a fault condition.
FEATURES AND CONTROLS
Remote LED Output — Use this to hook up the
remote LED supplied with the generator.The remote LED
will turn on and off in a series of blinks if certain faults are
detected in the generator.
Transfer Switch Communication — Use TxRx and
TxRx GND to transfer switch and optional wireless
StatStation™ to monitor generator functions.
+12 Volt DC, .5 Amp Output — Internal power supply.
10
Fault Contacts
Transfer Switch
Communication
Remote LED Output
+12 Volt DC, .5 Amp Output
240 Volt Utility